Powered by GoogleTranslate

Inspection Detail

Inspection: 122023575 - Anchor Glass Container Corp.

Inspection Information - Office: Allentown Area Office

 

Inspection Nr: 122023575
Report ID: 0317900
Date Opened: 10/07/1994

Site Address:
Anchor Glass Container Corp.
402 First Ave.
Royersford, PA 19468

Mailing Address:
4343 Anchor Plaza Pkwy., Tampa, FL 33634

Union Status: Union

SIC:3221

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/21/1994

Emphasis:

Case Closed: 08/04/1995


Related Activity
Type Activity Nr Safety Health
Accident 360918197
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $13,500 $0 $0 $0 $0 $13,500
Current Penalty $3,000 $0 $0 $0 $0 $3,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100332 B01 12/07/1994 01/09/1995 $1,000 $4,500 $0 12/19/1994 F - Formal Settlement  
2. 01001B Serious 19100332 B03 I 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  
3. 01001C Serious 19100332 B03 II 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  
4. 01001D Serious 19100332 B03 III 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  
5. 01001E Serious 19100333 C02 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  
6. 01001F Serious 19100334 C01 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  
7. 01002A Serious 19100333 A 12/07/1994 01/09/1995 $1,000 $4,500 $0 12/19/1994 F - Formal Settlement  
8. 01002B Serious 19100333 A02 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  
9. 01002C Serious 19100335 A01 I 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  
10. 01003A Serious 19100334 C02 12/07/1994 01/09/1995 $1,000 $4,500 $0 12/19/1994 F - Formal Settlement  
11. 01003B Serious 19100334 C03 12/07/1994 01/09/1995 $0 $0 $0 12/19/1994 F - Formal Settlement  

Investigation Summary

Investigation Nr: 170340822
Event: 09/21/1994
BURN - ELECTRICAL FAULT IN TEST EQUIPMENT

A maintenance mechanic climbed a stepladder to access a 4160-volt cutout box from which three cartridge fuses had been removed. The employee was apparently using a pigtail tester to test the circuit. The severely underrated tester failed, and the ensuing electric arc burned the employee. (The employee was working alone and unsupervised, so the exact cause of the accident was unknown. However, the tester was found on the floor in a burned and damaged condition.) He sustained second and third degree burns to his face, chest, arms, legs, and buttocks and died as a result of his injuries.

Keywords: BURN, CLOTHING, E GI V, ELECTRIC ARC, ELECTRICAL, MECHANIC, ELECTRICAL WORK, TEST EQUIPMENT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 122023575 Fatality Burn/Scald(Heat) Not specified mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.