Inspection Detail

Inspection: 121907208 - Ohio Power Company

Inspection Information - Office: Columbus Area Office

 

Inspection Nr: 121907208
Report ID: 0522500
Date Opened: 10/26/1998

Site Address:
Ohio Power Company
N.Muskingum Station,2303 Unionville Roadelysville
Mcconnelsville, OH 43756

Mailing Address:
1 Riverside Plaza, 24th Floor, Columbus, OH 43215

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/12/1998

Emphasis:

Case Closed: 03/22/1999


Related Activity
Type Activity Nr Safety Health
Accident 100750488
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 2 2
Initial Penalty $28,000 $0 $0 $0 $0 $28,000
Current Penalty $11,200 $0 $0 $0 $0 $11,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100147 C01 11/12/1998 12/15/1998 $7,000 $7,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19100147 C04 I 11/12/1998 11/22/1998 $7,000 $7,000 $0 I - Informal Settlement Citation has been deleted.
3. 01003 Serious 19100269 C 11/12/1998 03/12/1999 $4,200 $7,000 $0 I - Informal Settlement  
4. 01004 Serious 19100269 M03 V 11/12/1998 12/15/1998 $7,000 $7,000 $0 -  

Investigation Summary

Investigation Nr: 200750263
Event: 10/23/1998
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Four employees went to a substation to test potential transformers (PTs). One of the employees had been to the substation earlier and had deenergized the main transformer. This action did not, however, deenergize the PTs. The same employee climbed a 2.4-meter long ladder to remove the leads from one of the PTs with a conductive socket wrench. The employee was touching a grounded steel platform when he contacted the energized leads. He was electrocuted.

Keywords: PROTECTIVE GROUNDING, ELECTRICAL, ELECTROCUTED, LADDER, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 121907208 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.