Powered by GoogleTranslate

Inspection Detail

Inspection: 1215433 - Rabey Electric Co Inc

Inspection Information - Office: Savannah Area Office

 

Inspection Nr: 1215433
Report ID: 0418400
Date Opened: 05/25/1984

Site Address:
Rabey Electric Co Inc
Plant Mcintosh
Rincon, GA 31326

Mailing Address:
Po Box 23978, Savannah, GA 31403

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/13/1984

Emphasis:

Case Closed: 06/13/1984


Related Activity
Type Activity Nr Safety Health
Referral 900533472 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $450 $0 $0 $0 $0 $450
Current Penalty $450 $0 $0 $0 $0 $450
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260021 B02 07/06/1984 07/09/1984 $450 $450 $0 -  
2. 01001B Serious 19260450 A01 07/06/1984 07/09/1984 $0 $0 $0 -  
3. 01001C Serious 19260951 B01 07/06/1984 07/09/1984 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14348197
Event: 05/25/1984
ELECTRIC SHOCK AND BURNS - DIRECT CONTACT WITH LIVE PARTS

AN EMPLOYEE WAS INSTRUCTED BY HIS FOREMAN TO CLIMB AN 18.25-FOOT-HIGH SUBSTATION SWITCH STAND TO HELP INSTALL A 3-INCH BY 18-FOOT ALUMINUM BUS. THE BUS WAS TO RUN FROM THE CIRCUIT BREAKER TO THE SWITCH ON THE LOAD SIDE OF THE SWITCH STAND. HE WAS TO BOLT THE BUS TO THE SWITCH WITH HAND TOOLS. THE EMPLOYEE CLIMBED THE SWITCH STAND AND WALKED TOWARD THE OPPOSITE END OF THE STAND, WHERE THE SWITCH WAS LOCATED. WHEN HE REACHED THE CENTER OF THE STAND, HE RECEIVED AN ELECTRIC SHOCK FROM A 115-KILOVOLT SWITCH LOCATED ON THE OTHER SIDE OF THE SWITCH STAND. HE SUSTAINED SERIOUS BURNS ON THE LEFT SIDE OF HIS BODY AND LEG FRACTURES.

Keywords: BURN, CLOTHING, FRACTURE, ELECTRICAL, ELECTRIC SWITCH, E PTD, SUBSTATION, ELEC UTILITY WORK, ELECTRIC SHOCK, FALL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1215433 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.