Powered by GoogleTranslate

Inspection Detail

Inspection: 120657549 - Hawaiian Electric Co Inc

Inspection Information - Office: Hi-E-Honolulu

 

Inspection Nr: 120657549
Report ID: 0951510
Date Opened: 09/02/1993

Site Address:
Hawaiian Electric Co Inc
Queen Emma Sq
Honolulu, HI 96813

Mailing Address:
900 Richards St, Honolulu, HI 96813

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/28/1993

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 09/05/1994


Related Activity
Type Activity Nr Safety Health
Accident 360194377
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $4,500 $0 $0 $0 $0 $4,500
Current Penalty $0 $0 $0 $2,250 $0 $2,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 600002 B01 12/30/1993 09/15/1994 $2,250 $4,500 $0 P - Petition to Mod Abatement  

Investigation Summary

Investigation Nr: 744169
Event: 08/28/1993
BURN - ELECTRICAL FAULT IN SWITCH

A POWER LINE WORKER FOR AN ELECTRIC UTILITY WAS PERFORMING A ROUTINE SWITCHING OPERATION TO RESTORE A 4000-VOLT CIRCUIT TO NORMAL. HE ENTERED A SEMI-ENCLOSED SWITCHING AREA BETWEEN THE REAR OF CIRCUIT BREAKER PANEL AND THE DISCONNECT SWITCHES. HE WAS USING A LIVE-LINE TOOL WITH A CONDUCTIVE FUSE PULLER ON ITS END TO CLOSE THE DISCONNECT SWITCHES. AS HE WAS CLOSING THE LAST OF THE THREE SWITCHES, THE FUSE PULLER ASSEMBLY BRIDGED THE AIR GAP BETWEEN THE LEFT AND MIDDLE KNIFE BLADES. THIS CAUSED AN ELECTRICAL FAULT, AND THE ENSUING ELECTRIC ARC BURNED THE EMPLOYEE. HE WAS HOSPITALIZED FOR HIS INJURIES.

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, LIVE-LINE TOOL, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120657549 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.