Powered by GoogleTranslate

Inspection Detail

Inspection: 120306600 - Acx Inc

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 120306600
Report ID: 0950635
Date Opened: 12/20/1999

Site Address:
Acx Inc
2350 W 17th St
Long Beach, CA 90813

Mailing Address:
, , 00000

Union Status: Union

SIC:4731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/04/2000

Emphasis:

Case Closed: 02/08/2001


Related Activity
Type Activity Nr Safety Health
Accident 362024705
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3 6
Current Violations 2 3 5
Initial Penalty $7,288 $0 $0 $540 $0 $7,828
Current Penalty $4,500 $0 $0 $480 $0 $4,980
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23400021 01/07/2000 01/25/2000 $115 $130 $0 03/02/2000 J - ALJ Decision  
2. 01002 Other 23400022 A 01/07/2000 01/25/2000 $120 $135 $0 03/02/2000 J - ALJ Decision  
3. 01003 Other 342 A 01/07/2000 01/25/2000 $245 $275 $0 03/02/2000 J - ALJ Decision  
4. 02001 Serious 23400017 A01 01/07/2000 01/25/2000 $4,500 $5,000 $0 03/02/2000 J - ALJ Decision  
5. 03001 Serious 23200002 A 01/07/2000 01/12/2000 $0 $1,144 $0 03/02/2000 J - ALJ Decision Citation has been deleted.
6. 04001 Serious 23200002 A04 01/07/2000 01/12/2000 $0 $1,144 $0 03/02/2000 J - ALJ Decision  

Investigation Summary

Investigation Nr: 201032539
Event: 12/04/1999
burn - electrical fault in electrical cabinet

A machine operator was working for a large company that exported hay. The hay was processed and packed in a system of conveyors and mixer and extruder machines. The hay often jammed the mixer. The company's practice for freeing the conveyor was for the operator to open the door of a 480-volt electrical cabinet and reverse the polarity of mixer motor's supply conductors. This would reverse the motor's rotation and consequently free the mixer. On the day of the accident, with the mixer jammed, the operator knelt in front of the energized cabinet and crossed the conductors with a screwdriver. This caused an electrical fault, and the ensuing electric arc burned the employee. He suffered second- and third-degree burns on his face, neck, forearms, and legs. He was hospitalized for his injuries.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELECTRICAL CABINET, ELECTRICAL FAULT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120306600 Hospitalized injury Burn/Scald(Heat) Packaging and filling machine operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.