Powered by GoogleTranslate

Inspection Detail

Inspection: 120297130 - Xelectrix

Inspection Information - Office: Sacramento District Office

 

Inspection Nr: 120297130
Report ID: 0950621
Date Opened: 07/12/2007

Site Address:
Xelectrix
1015 2nd Street
Sacramento, CA 95814

Mailing Address:
7250 Auburn Blvd, #201, Citrus Heights, CA 95610

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/24/2007

Emphasis: S:Construction (Cship)

Case Closed: 07/03/2009


Related Activity
Type Activity Nr Safety Health
Accident 362333270
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 3 3
Initial Penalty $13,500 $0 $0 $500 $0 $14,000
Current Penalty $0 $0 $0 $500 $0 $500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 A 10/01/2007 10/15/2007 $125 $250 $0 10/17/2007 F - Formal Settlement  
2. 01002 Other 1509 C 10/01/2007 10/15/2007 $125 $250 $0 10/17/2007 F - Formal Settlement  
3. 02001 Other 23200002 A 10/01/2007 10/15/2007 $250 $13,500 $0 10/17/2007 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202485603
Event: 07/12/2007
Employee suffers electrical burns from arcing panel

On July 12, 2007, Employee #1 was assigned to report to a business to diagnose and repair electrical problems before it opened for the day. The business was in a three-story building, with the main electrical panel in the basement and sub-panels on the first and second floors. Employee #1 began working on the first floor panel while it was energized. He removed the panel cover, exposing the electrical components, then pulled out three circuit breakers to clean the corroded contact points. As he did this, he saw that the busbar was pitted, which made him think there had been episodes of overheating within the panel. He began scraping the contacts on a circuit breaker with a metal tool when he heard small arcing in the panel. There followed a thermal explosion with a fireball. Employee #1's clothing caught on fire, so he rolled on the floor to extinguish the flames, but the clothes kept burning. He then ran out of the building and again tried to extinguish the fire before he removed his shirt. He sustained first-,second-, and third-degree burns. He was transported by Emergency Services to the UC Davis Medical Center.

Keywords: BURN, REPAIR, ELECTRICIAN, CONSTRUCTION, LOCKOUT, CIRCUIT BREAKER, ELEC CIRC PART--MISC, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120297130 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.