Powered by GoogleTranslate

Inspection Detail

Inspection: 120259403 - Western Alied Air Conditioning Service

Inspection Information - Office: Monrovia District Office

 

Inspection Nr: 120259403
Report ID: 0950644
Date Opened: 02/07/2000

Site Address:
Western Alied Air Conditioning Service
2009 W.Chestnut Ave.
Alhambra, CA 91801

Mailing Address:
12046 E.Florence Ave., Santa Fe Springs, CA 90670

Union Status: Union

SIC:1711

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/25/2000

Planning Guide: Safety-Construction

Emphasis: S:Lead In Construction

Case Closed: 04/18/2000


Related Activity
Type Activity Nr Safety Health
Accident 362546756
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $0 $0 $0 $935 $0 $935
Current Penalty $0 $0 $0 $450 $0 $450
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 342 A 02/25/2000 03/25/2000 $0 $375 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Other 23200004 A 02/25/2000 03/25/2000 $450 $560 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201792702
Event: 02/02/2000
electric shock - direct contact with energized parts

A journeyman air conditioning repair worker and another employee were servicing a 208-volt, 2-ton unit on the roof of a building. The repair worker had over 22 years of experience in the trade and had worked for his employer for over 4 years. He removed the access door on the unit to check the refrigerant charge. On his knees leaning toward the unit, the repair worker located the refrigerant discharge access port, which was readily accessible. The refrigerant input port, however, was located toward the back of the unit and was obstructed by electrical components. With the unit running, the repair worker was removing the input port access cap when the back of his hand touched an unused terminal on a capacitor and received an electric shock. The coworker pushed the injured employee and broke the electrical contact. The repair worker received third-degree burns to his right hand and was transported to a hospital, where he was treated and released.

Keywords: E GI II, ELEC PROTECT EQUIP, REPAIR, ELECTRICAL, AIR CONDITIONER, ELECTROCUTED, LOCKOUT, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120259403 Non Hospitalized injury Electric Shock Heating, air conditioning, and refrig. mechanics
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close