Powered by GoogleTranslate

Inspection Detail

Inspection: 120212782 - Lompoc, City Of

Inspection Information - Office: Labor Enforcement Task Force (Letf) Unit - South

 

Inspection Nr: 120212782
Report ID: 0950645
Date Opened: 03/03/1995

Site Address:
Lompoc, City Of
100 Civic Center Plaza
Lompoc, CA 93438

Mailing Address:
, , 00000

Union Status: Union

SIC:9199

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 03/03/1995

Emphasis:

Case Closed: 11/04/1998


Related Activity
Type Activity Nr Safety Health
Accident 362182065
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 23200002 A01 06/05/1995 06/06/1995 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 170719850
Event: 02/28/1995
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A city maintenance department employee was working on the lighting system in a room in a city building. He was replacing all the ballasts in the lighting system as part of an energy conservation program. The employee had replaced about 500 ballasts; and, while he was working, the lighting circuits remained energized. (The supervisor stated that he had instructed the maintenance worker not to work with the circuits energized.) The employee's procedure had been to cut the ungrounded and grounded circuit conductors supplying the ballast. He would then put wire nuts on the ends of the two supply conductors and leave them hanging. Next, he would cut the secondary conductors coming from the ballast, remove the old ballast, install the new one, and reconnect the secondary conductors. He would complete the installation by connecting the ungrounded and grounded circuit conductors supplying the ballast after removing the wire nuts he had placed on their ends. While he was performing this procedure on one of the ballasts, he apparently contacted an energized part and was electrocuted.

Keywords: BALLAST--LIGHTING, LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120212782 Fatality Electric Shock Electrical and electronic technicians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.