Inspection Detail
Inspection: 1201888 - Proctor And Gamble Paper Products Co.
Inspection Information - Office: Atlanta East Area Office
Site Address:
Proctor And Gamble Paper Products Co.
U. S. 19 South
Albany, GA 31705
Mailing Address:
P. O. Box 1747, Albany, GA 31703
Union Status: NonUnion
SIC:2676
NAICS: 0
Inspection Type: Complaint
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 04/18/1985
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 08/07/1985
Type | Activity Nr | Safety | Health |
---|---|---|---|
Complaint | 71049613 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | ||||||
Initial Penalty | $280 | $0 | $0 | $0 | $0 | $280 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100261 B04 | 06/27/1985 | 06/29/1985 | $280 | $280 | $0 | I - Informal Settlement | Citation has been deleted. |
Investigation Summary
TWO EMPLOYEES WERE PERFORMING ROUTINE MAINTENANCE. THEY WERE MOVING A DRIVE SHAFT UNDERNEATH SOME ELECTRIC EQUIPMENT THAT WAS THOUGHT TO BE DEENERGIZED UNDER THE COMPANY'S LOCKOUT POLICY. HOWEVER, A 120-VOLT POWER SUPPLY LINE TO A CONTROL MOTOR WAS NOT DEENERGIZED WHEN THE 480-VOLT EQUIPMENT WAS LOCKED OUT. ADDITIONALLY, A PORTION OF THE 120-VOLT CIRCUIT WAS EXPOSED. THE SHAFT CAME INTO CONTACT WITH THE EXPOSED ENERGIZED PARTS, AND ONE OF THE EMPLOYEES RECEIVED A SEVERE ELECTRIC SHOCK.
Keywords: MAINTENANCE, E GI IV, ELECTRICAL, LOCKOUT, UNGUARDED LIVE PARTS, ELECTRIC CONDUCTOR, ELECTRIC SHOCK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 1201888 | Hospitalized injury | Electric Shock | Occupation not reported |