Powered by GoogleTranslate

Inspection Detail

Inspection: 120147764 - Alsco-Geyer

Inspection Information - Office: Sacramento District Office

 

Inspection Nr: 120147764
Report ID: 0950621
Date Opened: 05/09/2002

Site Address:
Alsco-Geyer
1/4 Mi South White Rd On 2047 Canal
Arbuckle, CA 95912

Mailing Address:
Po Box 111, Arbuckle, CA 95912

Union Status: NonUnion

SIC:0721

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/22/2002

Emphasis:

Case Closed: 03/31/2005


Related Activity
Type Activity Nr Safety Health
Accident 361712177
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 2 7
Current Violations 7 7
Initial Penalty $39,600 $0 $0 $1,050 $0 $40,650
Current Penalty $0 $0 $0 $2,060 $0 $2,060
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 B02 08/02/2002 08/19/2002 $275 $350 $0 01/31/2003 W - Empr Withdrew  
2. 01002 Other 3203 A 08/02/2002 08/19/2002 $275 $700 $0 01/31/2003 W - Empr Withdrew  
3. 02001 Other 23200001 A 08/02/2002 08/15/2002 $410 $18,000 $0 01/31/2003 W - Empr Withdrew  
4. 03001 Other 23200002 A01 08/02/2002 08/15/2002 $275 $5,400 $0 01/31/2003 W - Empr Withdrew  
5. 04001 Other 23200002 A02 08/02/2002 08/15/2002 $275 $5,400 $0 01/31/2003 W - Empr Withdrew  
6. 05001 Other 23200002 A03 08/02/2002 08/15/2002 $275 $5,400 $0 01/31/2003 W - Empr Withdrew  
7. 06001 Other 23200002 A05 08/02/2002 08/15/2002 $275 $5,400 $0 01/31/2003 W - Empr Withdrew  

Investigation Summary

Investigation Nr: 170873145
Event: 05/02/2002
Employee Sustains Burns in Electrical Fire

On May 5, 2002, Employee #1 was installing an Intermatic 24 hour Dial Time Switch (Model Number T103, 110-125 Volts). The installation was done with the system energized. He was installing the timer with the power on, 480 volts. He closed the breaker in the metal electrical box, and pulled power from the top of the breaker, which was energized. He connected the #1 and #2 wires from the timer to the starter and connected the #1 wire from the timer to the power lead. When he connected wire #2 from the timer to the power lead, there was an arch and a flash. The energized leads of #1 and #2 touched by way of the tool or lead wire and they arched, resulting in a flash and fire. The employee received second and third degree burns to his face arms and hands. He drove himself to a public telephone at a hunting club and waited for an ambulance. He was taken to UC Davis Burn Center in Sacramento, California. Employee #1 was hospitalized for more than seven days. The arch occurred at the live part of the breaker (the top), and not at the timer that he was installing. This would indicate that the energized leads of #1 and #2 touched by way of the tool or lead wire. A contributing factor to the accident was the failure of the employer to properly train the employee on his job duties as an electrician. The employee was using the wrong timer for the job, wrong tools, and pulled wire from the wrong place. The wire was connected to the energized side of the breaker and it should have been taken from the un- energized side of the breaker. NOTE: Event date in narrative is May 5, 2002 but the event date in IMIS summary is May 2, 2002.

Keywords: BURN, FIRE, ARM, FACE, UNTRAINED, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120147764 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close