Inspection Detail
Inspection: 120123906 - David Hilborn Dba Far West Marine Electric
Inspection Information - Office: Long Beach District Office
Site Address:
David Hilborn Dba Far West Marine Electric
900 Watson Center Road
Carson, CA 90749
Mailing Address:
419 Main Street #269, Huntington Beach, CA 92648
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/23/1999
Emphasis:
Case Closed: 07/25/2000
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362029233 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 2 | 5 | |||
| Current Violations | 3 | 3 | ||||
| Initial Penalty | $7,500 | $0 | $0 | $435 | $0 | $7,935 |
| Current Penalty | $0 | $0 | $0 | $1,375 | $0 | $1,375 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 342 A | 03/01/1999 | 03/29/1999 | $0 | $175 | $0 | 05/07/1999 | J - ALJ Decision | Citation has been deleted. |
| 2. | 01002 | Other | 3203 A | 03/01/1999 | 03/29/1999 | $175 | $260 | $0 | 05/07/1999 | J - ALJ Decision | |
| 3. | 02001 | Other | 23200003 | 03/01/1999 | 03/09/1999 | $600 | $1,500 | $0 | 05/07/1999 | J - ALJ Decision | |
| 4. | 03001 | Serious | 23200004 A02 | 03/01/1999 | 03/05/1999 | $0 | $3,000 | $0 | 05/07/1999 | J - ALJ Decision | Citation has been deleted. |
| 5. | 04001 | Other | 23200007 A | 03/01/1999 | 03/05/1999 | $600 | $3,000 | $0 | 05/07/1999 | J - ALJ Decision |
Investigation Summary
An electrician working for an electrical contractor was relocating machines on a customer's shop floor. As part of the work, he was relocating disconnect boxes. The boxes enclosed three-phase, 480-volt fusible-switch bus-duct plugs and were located on an overhead bus. The electrician had opened the switches for all the disconnects to which he would be making connections. However, he had not locked out those switches. As the electrician was terminating conductors connecting new wiring from machine to a disconnect box, a grounding conductor he was holding touched an energized conductor in the back of the disconnect box, causing an electrical fault. The ensuing electric arc burned the employee's face. He was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL BOX, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 120123906 | Hospitalized injury | Burn/Scald(Heat) | Electricians |