Inspection Detail
Inspection: 120082383 - Superior Industries International - California, In
Inspection Information - Office: Van Nuys District Office
Site Address:
Superior Industries International - California, In
7800 Woodley Ave.
Van Nuys, CA 91406
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3714
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/17/1996
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 10/01/1997
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362292021 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 3 | 3 | ||||
| Initial Penalty | $6,000 | $0 | $0 | $0 | $0 | $6,000 |
| Current Penalty | $6,000 | $0 | $0 | $0 | $0 | $6,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 23200002 A01 | 10/22/1996 | 10/25/1996 | $5,000 | $5,000 | $0 | - | ||
| 2. | 02001 | Serious | 23200002 A03 | 10/22/1996 | 11/08/1996 | $1,000 | $1,000 | $0 | - | ||
| 3. | 03001 | Serious | 23200002 A04 | 10/22/1996 | 11/08/1996 | $0 | $0 | $0 | - |
Investigation Summary
An employee was inspecting a panelboard to determine if it could be used to supply additional equipment to be installed in the area. He began to open an access door on one of the circuit breaker panels of a 480-volt distribution panelboard. He inserted a screwdriver into the access hole on the door to turn a screw and unlock a safety latch. The screw was missing, and the employee's screwdriver contacted an energized conductor, causing an electrical fault. The ensuing electric arc burned the employee. He sustained second- and third-degree burns to his right hand and first-degree burns to his back. The arc also singed his hair and eyebrows. He was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, ELECTRICAL, E GI VI, INSULATED TOOL, ELECTRICIAN, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 120082383 | Hospitalized injury | Burn/Scald(Heat) | Electricians |