Powered by GoogleTranslate

Inspection Detail

Inspection: 120057765 - P G & E

Inspection Information - Office: Labor Enforcement Task Force (Letf) Unit - South

 

Inspection Nr: 120057765
Report ID: 0950645
Date Opened: 01/07/1993

Site Address:
P G & E
11 & Long Branch
Grover City, CA 93433

Mailing Address:
P. O. Box 7779, San Francisco, CA 94120

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/20/1993

Emphasis:

Case Closed: 03/24/1994


Related Activity
Type Activity Nr Safety Health
Accident 361330137
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1
Initial Penalty $1,125 $0 $0 $150 $0 $1,275
Current Penalty $0 $0 $0 $150 $0 $150
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3235 F 02/03/1993 02/19/1993 $150 $150 $0 J - ALJ Decision  
2. 02001 Serious 2742 A03 02/03/1993 02/19/1993 $1,125 $1,125 $0 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 170695746
Event: 12/04/1992
ELECTRIC SHOCK - GROUND FAULT IN METAL SUPPORT STRUCTURE

A POWER LINE WORKER WAS ASSIGNED TO REPAIR AN OVERHEAD POWER LINE THAT WAS OUT BECAUSE OF AN ELECTRICAL STORM THE PREVIOUS NIGHT. ON ARRIVING AT THE SCENE, THE EMPLOYEE FOUND THAT A FUSE ON ONE TRANSFORMER OF A THREE-TRANSFORMER BANK HAD OPENED. HE GOT OUT EQUIPMENT, INCLUDING A HOT STICK, TO REPLACE THE FUSE. THE TRANSFORMERS WERE SUPPORTED BY AN H-FRAME STRUCTURE COMPRISING TWO WOODEN UTILITY POLES ABOUT 15 TO 20 FEET APART CONNECTED BY TWO METAL BEAMS AT A HEIGHT OF ABOUT 25 FEET. THE TWO METAL BEAMS SUPPORTED WOODEN CROSS BEAMS TO WHICH THE TRANSFORMERS WERE ATTACHED. THE METAL CROSS BEAMS WERE NOT GROUNDED, EVEN THOUGH THE TRANSFORMERS WERE. THE POWER LINE WORKER CLIMBED ONE OF THE POLES, HOLDING THE METAL BEAM FOR SUPPORT. HE THEN GRABBED A METAL CABLE, AROUND WHICH WAS WRAPPED A LOW-VOLTAGE CONDUCTOR TO STREETLIGHT POLE. APPARENTLY, THE METAL BEAM WAS ENERGIZED, AND HE RECEIVED AN ELECTRIC SHOCK. HE WAS ABLE TO FREE HIMSELF FROM THE CABLE AND CLIMBED DOWN THE POLE TO CALL FOR HELP. THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURY.

Keywords: STEEL BEAM, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, GROUND FAULT, ELEC UTILITY WORK, ELECTRIC SHOCK, TRANSFORMER, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120057765 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.