Powered by GoogleTranslate

Inspection Detail

Inspection: 120048699 - Chevron Products Company

Inspection Information - Office: Los Angeles District Office

 

Inspection Nr: 120048699
Report ID: 0950641
Date Opened: 12/20/1994

Site Address:
Chevron Products Company
324 W. El Segundo Blvd.
El Segundo, CA 90245

Mailing Address:
, , 00000

Union Status: Union

SIC:2911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/02/1995

Emphasis:

Case Closed: 02/28/1996


Related Activity
Type Activity Nr Safety Health
Accident 361297336
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $2,000 $0 $0 $0 $0 $2,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 3328 B 06/05/1995 06/19/1995 $2,500 $2,500 $0 06/20/1995 D - Govt Dismissed Citation has been deleted.
2. 02001 Serious 3328 G 06/05/1995 06/08/1995 $2,000 $2,500 $0 06/20/1995 F - Formal Settlement  

Investigation Summary

Investigation Nr: 170735302
Event: 12/07/1994
BURN - ELECTRICAL FAULT IN MOTOR CONTROL CENTER

An electrical trainer was asked to help troubleshoot a 480-volt circuit breaker at a motor control center at a coker unit. The circuit breaker was in the test position, and the cubicle door was open when the trainer arrived. He tried to close the door, but was not able to do so since some components were in the way. Checking to ensure that the circuit breaker was in the open position, the trainer started to rack in the breaker. An electrical fault occurred, and the trainer was burned by the ensuing electric arc. He was hospitalized with second and third degree burns to his hands and second degree burns to his face.

Keywords: BURN, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, CIRCUIT BREAKER, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 120048699 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close