Inspection Detail
Inspection: 120023080 - Thunder Electrical
Inspection Information - Office: San Francisco District Office
Site Address:
Thunder Electrical
150 Spear St.
San Francisco, CA 94105
Mailing Address:
, , 00000
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/08/1995
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/23/1995
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362188427 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $3,500 | $0 | $0 | $0 | $0 | $3,500 |
| Current Penalty | $0 | $0 | $0 | $110 | $0 | $110 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 23200002 A03 | 08/11/1995 | 08/16/1995 | $110 | $3,500 | $0 | I - Informal Settlement |
Investigation Summary
An electrician was troubleshooting a problem in a motor control center in a high rise building. A heating, ventilation, and air conditioning condenser water pump had tripped a circuit breaker. The employee apparently determined that the 480-volt terminal block containing the starter for the pump had shorted conductors and repaired it. As the employee tightened the lugs on the front of the terminal block in the process of reinstalling it, an electrical fault occurred. The ensuing electric arc burned him and knocked him backwards, unconscious, to the floor. It was believed that the cause of the fault was either that prongs at the rear of the block were not properly aligned and touched each other when tightened or that something behind fell onto the prongs.
Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL FAULT, ELEC EQUIPMENT--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 120023080 | Non Hospitalized injury | Burn/Scald(Heat) | Electricians |
Translate