Inspection: 119970424 - Imperial Irrigation District

Inspection Information - Office: San Bernardino District Office

 

Inspection Nr: 119970424
Report ID: 0950633
Date Opened: 08/12/1993

Site Address:
Imperial Irrigation District
Nw Corner Of Jefferson Street/Fiesta Drive
La Quinta, CA 92253

Mailing Address:
Post Office Box 937, Imperial, CA 92251

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/12/1993

Emphasis:

Case Closed: 08/10/1995


Related Activity
Type Activity Nr Safety Health
Accident 361257934
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 A 12/13/1993 12/13/1993 $0 $0 $0 J - ALJ Decision  
2. 02001 Serious 29400007 C03 12/13/1993 12/13/1993 $0 $0 $0 -  
3. 03001 Serious 2940 D 12/13/1993 12/13/1993 $0 $0 $0 12/29/1993 J - ALJ Decision  

Investigation Summary

Investigation Nr: 170605232
Event: 08/12/1993
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU POLE

AN ELECTRIC UTILITY CREW WAS PLACING A UTILITY POLE ON A 7200-VOLT OVERHEAD POWER LINE. THE NEW POLE WAS FRAMED, BALANCED AND ALIGNED PARALLEL TO THE POWER LINE, WITH TWO EMPLOYEES ON THE GROUND AND A FOREMAN OPERATING THE CONTROLS ON THE TRUCK CRANE BEING USED TO SET THE POLE. THE POLE WAS THEN RESET, BUTT HEAVY. THE TWO EMPLOYEES ON THE GROUND STARTED TO GO TOWARD THE BACK OF THE TRUCK TO GET THEIR GLOVES. AS ONE OF THEM WAS GOING AROUND THE BUTT OF THE POLE (TO THE LEFT REAR OF THE TRUCK), THE FOREMAN STARTED RAISING THE POLE. THE POLE GROUND, WHICH WAS COILED ON THE CROSSARM, CONTACTED ONE OF THE PHASE CONDUCTORS ON THE POWER LINE. AT THAT MOMENT, THE EMPLOYEE NEAR THE POLE TOUCHED THE GROUND WIRE ON THE POLE BUTT AND WAS ELECTROCUTED. THE CURRENT ENTRY AND EXIT POINTS WERE HIS RIGHT HAND AND HIS LEFT HIP. THE NORMAL PROCEDURE FOR THIS OPERATION WAS TO RAISE THE POLE AFTER COMPLETELY DEENERGIZING THE LINE. THE FOREMAN DID NOT ENFORCE THIS PROCEDURE.

Keywords: BOOM TRUCK, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119970424 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.