Powered by GoogleTranslate

Inspection Detail

Inspection: 119965598 - Imperial Irrigation

Inspection Information - Office: San Bernardino District Office

 

Inspection Nr: 119965598
Report ID: 0950633
Date Opened: 12/28/1992

Site Address:
Imperial Irrigation
42nd Ave And Lima Hall Street
Bermuda Dunes, CA 92201

Mailing Address:
81-600 Ave 58, La Quinta, CA 92253

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 12/30/1992

Emphasis:

Case Closed: 04/01/1993


Related Activity
Type Activity Nr Safety Health
Accident 361386584
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2941 J02 01/26/1993 01/26/1993 $0 $0 $0 -  
2. 02001 Serious 2941 I07B 01/26/1993 01/26/1993 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 170699128
Event: 12/28/1992
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CONDUCTOR

A JOURNEYMAN POWER LINE WORKER WAS WORKING ON A BULL TENSION CABLE TRAILER. HIS ASSIGNMENT WAS TO ADJUST THE TENSION ON THE CABLE AS IT WAS BEING STRUNG ON A SET OF 40-FOOT-TALL UTILITY POLES SUPPORTING A 12-KILOVOLT OVERHEAD POWER LINE. AS THE PULL CROSSED THE SECOND POLE, THE STEEL PULLING SOCK SNAGGED ONE OF THE CONDUCTORS ON THE 12-KILOVOLT SYSTEM. THE GROUND ROD AT THE PULLING EQUIPMENT WAS BLOWN OUT OF THE GROUND, AND THE CONDUCTOR BURNED IN HALF. THE MAIN BREAKER, WHICH WAS LOCATED 5 MILES AWAY, NEVER OPENED. THE POWER LINE WORKER WAS ELECTROCUTED. (ANOTHER POWER LINE WORKER DEENERGIZED THE PULLING EQUIPMENT BY CUTTING THE PHASE CONDUCTOR AFTER DEAD-ENDING IT.)

Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, TRAILER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119965598 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.