Inspection Detail
Inspection: 119959633 - Murrieta Hot Springs Resort & Spa
Inspection Information - Office: San Bernardino District Office
Site Address:
Murrieta Hot Springs Resort & Spa
39405 Murrieta Hot Springs Road
Murrieta, CA 92362
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:7011
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/25/1992
Emphasis:
Case Closed: 10/31/1992
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361401961 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $2,750 | $0 | $0 | $0 | $0 | $2,750 |
| Current Penalty | $2,750 | $0 | $0 | $0 | $0 | $2,750 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 2714 A | 10/29/1992 | 10/29/1992 | $2,750 | $2,750 | $0 | - |
Investigation Summary
A HEATING, VENTILATION, AND AIR CONDITIONING MAINTENANCE WORKER WAS ASSIGNED TO REPLACE THE MAIN BUS OF A 240/120-VOLT PANELBOARD. THE EXISTING BUS HAD "BURNED OUT". RATHER THAN DEENERGIZE AND LOCK OUT THE CIRCUIT BREAKER FEEDING THE PANELBOARD, THE EMPLOYEE ELECTED TO DEENERGIZE THE CIRCUIT AT THE 12-KILOVOLT PRIMARY TO A UTILITY COMPANY PAD-MOUNTED TRANSFORMER. THE EMPLOYEE FORCED OPEN THE LOCK ON THE PRIMARY SECTION AND DISCONNECTED THE ENERGIZED PRIMARY ELBOWS WITHOUT INCIDENT. HE THEN REPAIRED THE PANELBOARD AND RETURNED TO THE TRANSFORMER. AS HE WAS REPLACING THE ELBOWS ON THE TRANSFORMER, HIS SOCKET WRENCH CONTACTED THE TRANSFORMER HOUSING. THE ELECTRIC ARC CAUSED BY THIS ELECTRICAL FAULT SEVERELY BURNED THE EMPLOYEE'S ARM AND LEG. HE WAS HOSPITALIZED FOR AN EXTENDED PERIOD AS A RESULT OF HIS INJURIES. THE EMPLOYEE HAD BEEN PROVIDED WITH NEITHER TRAINING NOR PROTECTIVE EQUIPMENT.
Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, TRANSFORMER, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 119959633 | Hospitalized injury | Burn/Scald(Heat) | Heating, air conditioning, and refrig. mechanics |