Inspection: 119959633 - Murrieta Hot Springs Resort & Spa

Inspection Information - Office: San Bernardino District Office

 

Inspection Nr: 119959633
Report ID: 0950633
Date Opened: 08/25/1992

Site Address:
Murrieta Hot Springs Resort & Spa
39405 Murrieta Hot Springs Road
Murrieta, CA 92362

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:7011

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/25/1992

Emphasis:

Case Closed: 10/31/1992


Related Activity
Type Activity Nr Safety Health
Accident 361401961
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $2,750 $0 $0 $0 $0 $2,750
Current Penalty $2,750 $0 $0 $0 $0 $2,750
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2714 A 10/29/1992 10/29/1992 $2,750 $2,750 $0 -  

Investigation Summary

Investigation Nr: 170699045
Event: 08/15/1992
BURN - ELECTRICAL FAULT IN TRANSFORMER

A HEATING, VENTILATION, AND AIR CONDITIONING MAINTENANCE WORKER WAS ASSIGNED TO REPLACE THE MAIN BUS OF A 240/120-VOLT PANELBOARD. THE EXISTING BUS HAD "BURNED OUT". RATHER THAN DEENERGIZE AND LOCK OUT THE CIRCUIT BREAKER FEEDING THE PANELBOARD, THE EMPLOYEE ELECTED TO DEENERGIZE THE CIRCUIT AT THE 12-KILOVOLT PRIMARY TO A UTILITY COMPANY PAD-MOUNTED TRANSFORMER. THE EMPLOYEE FORCED OPEN THE LOCK ON THE PRIMARY SECTION AND DISCONNECTED THE ENERGIZED PRIMARY ELBOWS WITHOUT INCIDENT. HE THEN REPAIRED THE PANELBOARD AND RETURNED TO THE TRANSFORMER. AS HE WAS REPLACING THE ELBOWS ON THE TRANSFORMER, HIS SOCKET WRENCH CONTACTED THE TRANSFORMER HOUSING. THE ELECTRIC ARC CAUSED BY THIS ELECTRICAL FAULT SEVERELY BURNED THE EMPLOYEE'S ARM AND LEG. HE WAS HOSPITALIZED FOR AN EXTENDED PERIOD AS A RESULT OF HIS INJURIES. THE EMPLOYEE HAD BEEN PROVIDED WITH NEITHER TRAINING NOR PROTECTIVE EQUIPMENT.

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, TRANSFORMER, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119959633 Hospitalized injury Burn/Scald(Heat) Heating, air conditioning, and refrig. mechanics
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.