Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 119947521 - Cadri Company, Inc

Inspection Information - Office: Ca San Bernardino

 

Inspection Nr: 119947521
Report ID: 0950633
Open Date: 05/22/2000

Site Address:
Cadri Company, Inc
6905 Kimball Ave
Chino, CA 91710

Mailing Address:
540 Third Street, Lake Elsinore, CA 92530

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Health

Close Conference: 11/16/2000

Emphasis:

Close Case:02/11/2011


Related Activity
Type Activity Nr Safety Health
Accident 362448920
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 3 5
Current Violations 1 4 5
Initial Penalty $31,500 $0 $0 $785 $0 $32,285
Current Penalty $12,600 $0 $0 $225 $0 $12,825
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 A 11/16/2000 12/19/2000 $225 $225 $0 -  
2. 01002 Other 5158 C01 A 11/16/2000 11/21/2000 $0 $110 $0 12/28/2000 J - ALJ Decision  
3. 01003 Other 5158 C02 11/16/2000 12/19/2000 $0 $450 $0 12/28/2000 J - ALJ Decision  
4. 02001 Serious 5158 D03 11/16/2000 11/21/2000 $12,600 $15,750 $0 12/28/2000 J - ALJ Decision  
5. 03001 Other 5158 D06 11/16/2000 11/21/2000 $0 $15,750 $0 12/28/2000 J - ALJ Decision  

Investigation Summary

Investigation Nr: 201153764
Event: 05/22/2000
Employees Asphyxiated While Working In Manhole

Two employees of an electrical contractor were working in a 7.9-meter-deep sump manhole at a water desalination facility site under construction. An employee of a general contractor found the employees unconscious at the bottom of the manhole. An outside rescue service from a local fire department responded and found the atmosphere in the manhole to contain 8 percent oxygen at the bottom of the sump. The two employees died of hypoxic asphyxia. Postaccident evaluations found oxygen levels as low as 2 percent and elevated levels of nitrogen and carbon dioxide. The sump was found to be in contact with warm, moist soil through a series of interconnected perforated pipes designed to drain excess groundwater. It was suspected that biological activity in the surrounding soil consumed the available oxygen and generated excess levels of nitrogen and carbon dioxide.

Keywords:oxygen deficiency, unconsciousness, asphyxiated, confined space, manhole

Investigated Inspection
# Inspection Age Sex Degree Nature Occupation
1 119947521 Fatality Asphyxia Supervisors; electricians & power transm. install.
2 119947521 Fatality Asphyxia Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close