Powered by GoogleTranslate

Inspection Detail

Inspection: 119947158 - Viceroy Gold Corporation

Inspection Information - Office: Sacramento Mining & Tunneling District Office

 

Inspection Nr: 119947158
Report ID: 0950651
Date Opened: 05/12/1999

Site Address:
Viceroy Gold Corporation
115575 Hart Mine Road
Ivanpah, CA 92309

Mailing Address:
Po Box 68, Searchlight, NV 89046

Union Status: NonUnion

SIC:1041

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/27/1999

Emphasis: L:Tunnel

Case Closed: 07/26/2001


Related Activity
Type Activity Nr Safety Health
Accident 362476210
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 2 2
Initial Penalty $10,220 $0 $0 $0 $0 $10,220
Current Penalty $5,435 $0 $0 $0 $0 $5,435
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 1541 B01 07/16/1999 05/14/1999 $935 $1,220 $0 01/25/2000 J - ALJ Decision  
2. 02001 Serious 29400001 A 07/16/1999 05/14/1999 $4,500 $4,500 $0 01/25/2000 J - ALJ Decision Citation has been deleted.
3. 03001 Serious 2943 D03 07/16/1999 05/14/1999 $4,500 $4,500 $0 01/25/2000 J - ALJ Decision  

Investigation Summary

Investigation Nr: 170847669
Event: 05/11/1999
BURN - ELECTRIC METER FAILED

A crew of employees a remote gold mine was digging with a backhoe when they cut a 4160-volt underground power line. A journeyman electrician was assigned to troubleshoot the problem, and restore power to the high-voltage equipment. The 58-year-old electrician had a wealth of experience, including 20 years of high-voltage experience. After resetting the circuit breakers protecting the circuit, the electrician got a 1000-volt Fluke meter. He had assumed that the broken line was a 480-volt line. He entered the excavation without wearing rubber insulating gloves and checked the circuit with the meter. (The employer had high-voltage testing equipment and rubber insulating gloves available.) The meter failed, and the ensuing electric arc burned the employee. He was hospitalized with second- and third-degree burns on his face and hands.

Keywords: BURN, E GI V, ELECTRIC ARC, REPAIR, ELECTRICAL, PPE, ELECTRICIAN, ELECTRICAL WORK, ELECTRIC METER, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119947158 Hospitalized injury Burn(Chemical) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close