Powered by GoogleTranslate

Inspection Detail

Inspection: 119914356 - City Of Ventura

Inspection Information - Office: Labor Enforcement Task Force (Letf) Unit - South

 

Inspection Nr: 119914356
Report ID: 0950645
Date Opened: 02/25/1993

Site Address:
City Of Ventura
Water Treatment Plant
Ventura, CA 93002

Mailing Address:
5895 N. Ventura Ave., Ventura, CA 93002

Union Status: Union

SIC:4952

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 03/16/1993

Emphasis:

Case Closed: 07/10/1995


Related Activity
Type Activity Nr Safety Health
Accident 362158396
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 4 4
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2711 03/30/1993 03/31/1993 $0 $0 $0 -  
2. 02001 Serious 2860 03/30/1993 03/31/1993 $0 $0 $0 -  
3. 03001 Serious 29400002 A01 03/30/1993 03/31/1993 $0 $0 $0 -  
4. 04001 Serious 23200004 A02 03/30/1993 03/31/1993 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 170152185
Event: 02/24/1993
ELECTRIC SHOCK - CONTACT WITH LIVE PARTS THRU METER LEADS

AN ELECTRICIAN AT A CITY WATER TREATMENT PLANT WAS TROUBLESHOOTING AN ELECTRICAL FAULT IN A LOW-VOLTAGE AC CONTROL CIRCUIT. THE CONTROL CIRCUITS WERE IN THE SAME ENCLOSURE AS A 2500-VOLT, THREE-PHASE CIRCUIT USED TO SUPPLY BOOSTER PUMPS. THE CABINET HOUSING THE CIRCUITS WAS AN SAF 400 UNIT WITH A 50-KILOVOLT INTERRUPTER WITH A VQ CONTACTOR (SERIAL NO. 5-76-1807-21) TO SWITCH THE HIGH VOLTAGE CIRCUIT. THE EMPLOYEE BY-PASSED THE INTERLOCK, SO THE CONTACTOR REMAINED ENERGIZED AT 5000 VOLTS. HE WAS USING A MULTIMETER TO CHECK THE LOW-VOLTAGE CIRCUIT WHEN HE INADVERTENTLY CONTACTED PARTS OF THE HIGH-VOLTAGE CIRCUIT WITH THE METER'S TEST LEADS. THE EMPLOYEE, WHO WAS NOT USING ELECTRICAL PROTECTIVE EQUIPMENT, WAS BURNED ON HIS FACE, CHEST, AND ARMS. HE WAS TRANSPORTED TO A BURN CENTER, WHERE HE WAS HOSPITALIZED FOR HIS INJURIES.

Keywords: BURN, CLOTHING, E GI II, ELEC PROTECT EQUIP, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119914356 Hospitalized injury Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.