Inspection Detail
Inspection: 119894731 - Indio Housing Development Corporation
Inspection Information - Office: San Bernardino District Office
Site Address:
Indio Housing Development Corporation
47-155 Van Buren #190
Indio, CA 92201
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:1522
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/15/1994
Emphasis:
Case Closed: 12/20/1994
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362241242 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 3 | 5 | |||
| Current Violations | 2 | 3 | 5 | |||
| Initial Penalty | $3,500 | $0 | $0 | $770 | $0 | $4,270 |
| Current Penalty | $3,500 | $0 | $0 | $770 | $0 | $4,270 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 342 A | 10/06/1994 | 10/06/1994 | $250 | $250 | $0 | - | ||
| 2. | 01002 | Other | 3203 A03 | 10/06/1994 | 10/06/1994 | $260 | $260 | $0 | - | ||
| 3. | 01003 | Other | 5194 E01 | 10/06/1994 | 10/06/1994 | $260 | $260 | $0 | - | ||
| 4. | 02001 | Serious | 3279 D11 | 10/06/1994 | 10/06/1994 | $1,750 | $1,750 | $0 | - | ||
| 5. | 03001 | Serious | 23200004 A02 | 10/06/1994 | 10/06/1994 | $1,750 | $1,750 | $0 | - |
Investigation Summary
An employee and his supervisor, who were employed by a company that maintains housing for migrant farm workers, were replacing a sodium vapor lamp. Three lighting standards were supplied by the 120-volt lighting circuit, and one of the lamps had been broken by a BB pellet. The photocell controlling the circuit was broken, and the other two lamps were lit. (The employee and his supervisor knew that the lighting fixture was energized.) The supervisor furnished an 18-foot metal extension ladder and placed it in the bed of a pickup truck so that the employee could reach the top of the 25-foot-tall lighting standard. While he was removing the broken lamp, the employee contacted an energized part on the secondary side of the ballast. He received an electric shock, which knocked him off the ladder and caused him to fall into the truck. The employee sustained electrical burns to his feet and injured his neck and back as a result of the fall. He was hospitalized for his injuries.
Keywords: E GI IV, ELECTRICAL, LADDER, LIGHTING FIXTURE, ELECTRICAL WORK, LOCKOUT, METAL LADDER, ELEC CIRC PART--MISC, ELECTRIC SHOCK, FALL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 119894731 | Hospitalized injury | Burn/Scald(Heat) | Not specified mechanics and repairers |