Powered by GoogleTranslate

Inspection Detail

Inspection: 119865236 - Graphic Electric

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 119865236
Report ID: 0950642
Date Opened: 12/11/1995

Site Address:
Graphic Electric
3217 Garfield Ave
Commerce, CA 90023

Mailing Address:
4975 Valley Bl, Los Angeles, CA 90032

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/17/1996

Emphasis:

Case Closed: 09/13/2010


Related Activity
Type Activity Nr Safety Health
Accident 362172702
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $0 $0 $0 $1,300 $0 $1,300
Current Penalty $0 $0 $0 $1,300 $0 $1,300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200002 A01 05/17/1996 06/19/1996 $650 $650 $0 -  
2. 01002 Other 23200002 A02 05/17/1996 06/19/1996 $650 $650 $0 -  

Investigation Summary

Investigation Nr: 170736185
Event: 11/25/1995
BURN - ELECTRICAL FAULT IN ELECTRIC SWITCH

An electrician and his helpers were sent to a jobsite to install 700-MCM conductors to the main panelboard inside a building. The conductors were to be run from the main disconnect cabinet for a 16.5-kilovolt-ampere distribution transformer feeding the panelboard. The electrician was working without electrical protective equipment, safety glasses, and hardhat. Without following the procedure that had been established for deenergizing the 480-volt circuit, the electrician reached into an energized area and manually disconnected a knife switch in one cabinet as part of an improvised procedure. He did the same thing in a second cabinet, and the second switch failed and caused an electrical fault. The electrician received an electric shock and was burned by the ensuing electric arc. He was hospitalized with burns to his hands, face, and other parts of his body.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC SHOCK, ELECTRICAL CABINET, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119865236 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close