Inspection Detail
Inspection: 119864650 - Systems Electric
Inspection Information - Office: Long Beach District Office
Site Address:
Systems Electric
15514 Paramount Blvd
Paramount, CA 90723
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/13/1995
Emphasis:
Case Closed: 02/22/1996
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362169021 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $0 | $100 | $0 | $100 |
| Current Penalty | $0 | $0 | $0 | $100 | $0 | $100 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 342 A | 10/12/1995 | 11/14/1995 | $100 | $100 | $0 | - |
Investigation Summary
An electrician was working on a main circuit breaker panelboard. He took the cover off a portion of the panelboard to expose a circuit breaker that was going to be replaced later that week. He planned to replace the circuit breaker as soon as negotiations for plant shutdown were made, when the panelboard could be deenergized. However, as part of preparatory work, the electrician was working on mountings for the replacement circuit breaker with the panelboard energized. A phase-to-phase electrical fault occurred. The ensuing electric arc burned the electrician's hands. In reaction, he dropped his wrench, and a second electrical fault occurred as he was trying to get away. The second fault occurred within seconds of the first. The employee was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, HAND
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 119864650 | Hospitalized injury | Burn/Scald(Heat) | Electricians |
Translate