Inspection Detail
Inspection: 119863975 - Belkin Components
Inspection Information - Office: Long Beach District Office
Site Address:
Belkin Components
5715 Bickett St
Huntington Park, CA 90255
Mailing Address:
1303 Walnut Parkway, Compton, CA 90220
Union Status: NonUnion
SIC:3823
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/28/1994
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 12/18/1995
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 362166233 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $7,500 | $0 | $0 | $0 | $0 | $7,500 |
Current Penalty | $0 | $0 | $0 | $400 | $0 | $400 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 23200002 A | 12/01/1994 | 01/03/1995 | $400 | $7,500 | $0 | 12/27/1994 | W - Empr Withdrew |
Investigation Summary
An electrical technician was working from a scissor lift, installing a communication cable. He was working near the 480-volt, three-phase runway conductors for an overhead crane. The electric power to the crane was not deenergized, and the employee was not using electrical protective equipment. As he was feeding the communication cable with left hand, his right wrist contacted one of the outer and the inner runway conductors. The employee received an electric shock. He yelled for help, and other employees ran to open the circuit breaker protecting the circuit. When the employees opened the circuit breaker, the injured employee collapsed to the floor of the scissor lift. He was hospitalized for his injury.
Keywords: UNCONSCIOUSNESS, E GI IV, ELECTRICAL, RUNWAY CONDUCTOR, LOCKOUT, ELECTRIC SHOCK, AERIAL LIFT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 119863975 | Hospitalized injury | Electric Shock | Electrical and electronic technicians |