Powered by GoogleTranslate

Inspection Detail

Inspection: 119861672 - La County Mta

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 119861672
Report ID: 0950642
Date Opened: 03/23/1994

Site Address:
La County Mta
13504 Willowbrook Ave
Los Angeles, CA 90059

Mailing Address:
425 S Main St, Los Angeles, CA 90013

Union Status: Union

SIC:4111

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 06/01/1994

Emphasis:

Case Closed: 06/01/1994


Related Activity
Type Activity Nr Safety Health
Accident 362160012
Accident 362164188
Accident 362164345
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 2940 D 06/01/1994 06/01/1994 $0 $0 $0 06/20/1994 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 170631048
Event: 03/14/1994
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A three-person crew for a metropolitan transit company was cleaning switchgear in a substation on an electric railway system. The substation was supplied by a 16.5-kilovolt overhead power line owned by an electric utility company. The substation coverts the 16.5 kilovolts AC to the 700 volts DC used on the railway. The main circuit breakers feeding the substation were opened and locked out with padlocks. Two of the power line workers were inside the substation, vacuuming dust from the switchgear. The third power line worker was outside the substation. While kneeling, he contacted a lightning arrester connected to the supply side of the main station circuit breakers and received an electric shock. (The current entry and exit points were his hand and his knee.) He died of electrocution in a hospital about 1 hour after the accident.

Keywords: ELEC PROTECT EQUIP, RAILWAY CIRCUIT, LIGHTNING ARRESTER, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, SUBSTATION, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119861672 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.