Inspection Detail
Inspection: 119830099 - Shamma Electric
Inspection Information - Office: Monrovia District Office
Site Address:
Shamma Electric
South End Of Catalina At Cornell
Pasadena, CA 91344
Mailing Address:
11255 Ruffner Ave, Granada Hills, CA 91344
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 11/03/1995
Emphasis:
Case Closed: 06/12/1997
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361365257 | ||
| Accident | 362258600 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $9,000 | $0 | $0 | $0 | $0 | $9,000 |
| Current Penalty | $0 | $0 | $0 | $700 | $0 | $700 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 23200001 A | 11/03/1995 | 11/17/1995 | $350 | $3,000 | $0 | 12/05/1995 | J - ALJ Decision | |
| 2. | 02001 | Other | 23200003 | 11/03/1995 | 11/17/1995 | $350 | $3,000 | $0 | 12/05/1995 | J - ALJ Decision | |
| 3. | 03001 | Serious | 3203 A | 11/03/1995 | 11/17/1995 | $0 | $3,000 | $0 | 12/05/1995 | J - ALJ Decision | Citation has been deleted. |
Investigation Summary
An electrician was working from a fiberglass stepladder, installing a fluorescent lighting fixture in the ceiling. He had not deenergized the 277-volt lighting circuit before he started installing the fixture. He apparently brought one of the circuit conductors into contacted with the T-bars supporting the dropped ceiling and caused an electrical fault. The ensuing electric arc burned the employee on his palms and chest. He was hospitalized in a burn center for about 2 months.
Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 119830099 | Hospitalized injury | Electric Shock | Electricians |
Translate