Powered by GoogleTranslate

Inspection Detail

Inspection: 119745974 - Pacific Gas And Electric Company

Inspection Information - Office: Foster City District Office

 

Inspection Nr: 119745974
Report ID: 0950613
Date Opened: 02/11/1997

Site Address:
Pacific Gas And Electric Company
31 Anderson Way
Menlo Park, CA 94025

Mailing Address:
P. O. Box 7017, San Francisco, CA 94120

Union Status: Union

SIC:4931

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/20/1997

Emphasis:

Case Closed: 12/31/1998


Related Activity
Type Activity Nr Safety Health
Accident 362301517
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 1 1 2
Initial Penalty $10,000 $0 $0 $675 $0 $10,675
Current Penalty $5,000 $0 $0 $225 $0 $5,225
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 5158 D02 06/20/1997 07/17/1997 $0 $450 $0 08/20/1997 F - Formal Settlement Citation has been deleted.
2. 01002 Other 5158 D03 06/20/1997 02/11/1997 $225 $225 $0 08/20/1997 F - Formal Settlement  
3. 02001 Serious 2717 06/20/1997 07/17/1997 $0 $5,000 $0 08/20/1997 F - Formal Settlement Citation has been deleted.
4. 03001 Serious 29400002 A 06/20/1997 02/11/1997 $5,000 $5,000 $0 08/20/1997 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201120086
Event: 01/27/1997
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A power line worker and his supervisor had pumped water from an underground electrical vault. The power line worker entered the vault and attached a rope to the switch handle of a 15-kilovolt, 400-ampere T-GRAM oil switch, which controlled a transformer in the same vault. He had attached the rope so that he could operate the handle from outside the vault. The switch handle had three positions: on, off, and test; and the employee was going to use the rope to pull the handle from the on position to the off position. Unfortunately, when he pulled the rope, the handle went past the off position to the test position. A metal block used to prevent this from happening was not in place. The supervisor and the power line worker assumed that the handle was in the off position even though a brief inspection would have revealed it was not. (The switch was visible to both from outside the vault.) When the power line worker reentered the vault to remove the rope, he contacted an unguarded, energized bushing on the oil switch and received an electric shock. He was hospitalized with serious injuries.

Keywords: ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, LOCKOUT, E PTD, UNDRGRD INSTALLATION, ELEC UTILITY WORK, ELECTRIC SHOCK, INATTENTION

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119745974 Hospitalized injury Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close