# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 5162 A | 01/24/1995 | 02/28/1995 | $75 | $75 | $0 | 02/21/1995 | W - Empr Withdrew | |
2. | 01002 | Other | 5164 A | 01/24/1995 | 01/27/1995 | $75 | $75 | $0 | 02/21/1995 | W - Empr Withdrew | |
3. | 02001 | Other | 4184 B | 01/24/1995 | 01/27/1995 | $260 | $725 | $0 | 02/21/1995 | J - ALJ Decision |
Investigation Summary
After an exothermic reaction of magnesium oxide and leaching water in an ozone generator, the "ozone destruct" piping (18 in. by 2 in. diameter) was cleaned out and filled with activated carbon. About 18 hours later, the chemical reaction of the incompatible activated carbon and ozone caused an explosion that blew up the generator. No one was in the room; there were no injuries. An accident-related citation was issued for violation of G 8CCR 5164(a).
Keywords: EXPLOSION, CHEMICAL REACTION
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 119698249 | Occupation Not Listed |