Powered by GoogleTranslate

Inspection Detail

Inspection: 119690261 - El Camino Hospital

Inspection Information - Office: Fremont District Office

 

Inspection Nr: 119690261
Report ID: 0950612
Date Opened: 04/19/2001

Site Address:
El Camino Hospital
2500 Grant Rd., P.O. Box 7025
Mountain View, CA 94039

Mailing Address:
, , 00000

Union Status: Union

SIC:8062

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/16/2001

Emphasis:

Case Closed: 11/27/2001


Related Activity
Type Activity Nr Safety Health
Accident 101799989
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 4 9
Current Violations 5 4 9
Initial Penalty $26,880 $0 $0 $930 $0 $27,810
Current Penalty $26,880 $0 $0 $930 $0 $27,810
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23400022 A 09/26/2001 10/13/2001 $185 $185 $0 -  
2. 01002 Other 3314 H 09/26/2001 10/13/2001 $185 $185 $0 -  
3. 01003 Other 3203 B01 09/26/2001 10/29/2001 $375 $375 $0 -  
4. 01004 Other 3276 B 09/26/2001 10/13/2001 $185 $185 $0 -  
5. 02001 Serious 23950045 A 09/26/2001 10/13/2001 $3,375 $3,375 $0 -  
6. 03001 Serious 23400017 A 09/26/2001 10/13/2001 $335 $335 $0 -  
7. 04001 Serious 4851 M 09/26/2001 10/13/2001 $335 $335 $0 -  
8. 05001 Serious 25000007 B 09/26/2001 10/13/2001 $335 $335 $0 -  
9. 06001 Serious 23400001 09/26/2001 10/13/2001 $22,500 $22,500 $0 -  

Investigation Summary

Investigation Nr: 202312849
Event: 04/13/2001
Electric Shock - Ground Fault in Electric Welder

An employee had a work order to repair a leaking pipe on a water softener in a boiler room. The work required welding and cutting with an electric welder. The employee brought a Miller Arc welder with him to the boiler room. The boiler room did not provide a suitable electric outlet for the welder, so the employee obtained a 480-volt, three-phase pigtail extension cord adapter. The adapter had three alligator clips at one end. The employee connected the alligator clips to a 15-ampere circuit breaker in a motor panelboard and connected the cord connector on the adapter to the attachment plug on the welder's power supply cord. When he energized the welder, the circuit breaker tripped. Following written instructions, the employee notified the chief engineer, who determined that the welder's internal wiring was set at 240 volts. The chief engineer and the employee adjusted the wiring so that the welder could run on 480 volts. The employee operated the welder with no problems for the rest of the day, and he used the welder for approximately 1 hour over that period. At the end of the day, he turned off the welder and the circuit breaker and stored the welder in the boiler room overnight. The next day, the employee, who was accompanied by a coworker, returned to the boiler room to finish his work. A fixed metal ladder to an overhead work area was near the welder. The employee connected the welder and turned on the circuit breaker. The two employees were discussing the proper way to proceed with the work. The coworker was leaning on the welder, and the employee was on the other end. The employee placed his right foot on the bottom rung on the ladder and his right hand on the ladder and then touched the handle on the welder. He received an electric shock and could not let go of the welder. He was finally able to break himself from the ladder rung and fell to the concrete floor. He was hospitalized with a fractured hip. The equipment grounding conductor on the welder's attachment plug had been attached to an ungrounded circuit conductor.

Keywords: E GI V, ELECTRICAL, WELDER, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC SHOCK, FALL, UNTRAINED, EQUIPMENT APPROVAL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119690261 Hospitalized injury Fracture Stationary engineers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.