Powered by GoogleTranslate

Inspection Detail

Inspection: 119643104 - City Of Sunnyvale Public Works Department

Inspection Information - Office: Fremont District Office

 

Inspection Nr: 119643104
Report ID: 0950612
Date Opened: 03/24/2006

Site Address:
City Of Sunnyvale Public Works Department
221 Commercial
Sunnyvale, CA 94086

Mailing Address:
, , 00000

Union Status: Union

SIC:7538

NAICS: 811111/General Automotive Repair


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 05/08/2006

Emphasis:

Case Closed: 08/14/2006


Related Activity
Type Activity Nr Safety Health
Accident 102452364
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23400001 05/11/2006 08/15/2006 $0 $0 $0 A - Amendment  

Investigation Summary

Investigation Nr: 202315743
Event: 11/29/2005
Employee Suffers Electrical Shock, Is Hospitalized

At approximately 3:00 p.m. on November 29, 2005, Employee #1 was removing a cover of an electrical receptacle to check the outlet and received an electrical shock. Employee #1 was repairing to machine-turn a set of brake rotors at the brake lathe in the fleet shop. As part of completing the turning of rotors, the drill motor with a cleaning disc is used. When Employee #1 plugged the drill motor into the receptacle, he noticed the receptacle was loose. Employee #1 removed the cover plate to the receptacle and inspected it for any loose wiring. The wiring appeared to be secured. Employee #1 began to tighten the top hold-down screw of the receptacle, using both hands (his right hand holding the screwdriver and left hand as a guide to the screw). When the screw driver made contact with the screw, Employee #1 received an intense electrical shock. The facilities maintenance staff determined that the wiring behind the receptacle had a fault. Exposed portion of hot wire had come in contact with the plug's retaining screw. The situation caused the J-box to become energized so that when Employee #1 made contact with the box via his screwdriver he became a conduit to ground and was shocked with 120-volts of electrical power. Employee #1 was brought to the hospital and was released the following day.

Keywords: LATHE, ELECTRIC CABLE, LIGHTING FIXTURE, ELEC CIRC PART--MISC, ELECTRIC SHOCK, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119643104 Hospitalized injury Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close