Inspection Detail
Inspection: 119605582 - Neary & Sons Corporation
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address:
Neary & Sons Corporation
2361 Solomons Island Road
Annapolis, MD 21401
Mailing Address:
923 Gist Avenue, Silver Spring, MD 20910
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/12/1995
Emphasis:
Case Closed: 01/04/1996
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 360229017 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | ||||
Current Violations | 1 | 1 | ||||
Initial Penalty | $625 | $0 | $0 | $0 | $0 | $625 |
Current Penalty | $625 | $0 | $0 | $0 | $0 | $625 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260416 A01 | 10/06/1995 | 10/12/1995 | $625 | $625 | $0 | - |
Investigation Summary
An electrician was working from a Maxi-Lift mobile work platform, splicing conductors at ceiling level. The conductors on which he was working were deenergized, but others in the area were still energized. The employee pushed the 480/277-volt energized conductors out of the way. He pushed them against a 152-mm-deep, 305-mm by 305-mm, metal electrical box, and the edge of the box pierced the electrical tape covering a splice on one of the energized conductors. (The employee had believed that the tape was sufficient protection.) The resulting electrical fault caused an electric arc that burned the electrician's body. He was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL BOX, ELECTRICAL FAULT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 119605582 | Hospitalized injury | Electric Shock | Electricians |