Powered by GoogleTranslate

Inspection Detail

Inspection: 119605582 - Neary & Sons Corporation

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 119605582
Report ID: 0352440
Date Opened: 05/26/1995

Site Address:
Neary & Sons Corporation
2361 Solomons Island Road
Annapolis, MD 21401

Mailing Address:
923 Gist Avenue, Silver Spring, MD 20910

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/12/1995

Emphasis:

Case Closed: 01/04/1996


Related Activity
Type Activity Nr Safety Health
Accident 360229017
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $625 $0 $0 $0 $0 $625
Current Penalty $625 $0 $0 $0 $0 $625
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 10/06/1995 10/12/1995 $625 $625 $0 -  

Investigation Summary

Investigation Nr: 170069025
Event: 05/26/1995
BURN - ELECTRICAL FAULT IN JUNCTION BOX

An electrician was working from a Maxi-Lift mobile work platform, splicing conductors at ceiling level. The conductors on which he was working were deenergized, but others in the area were still energized. The employee pushed the 480/277-volt energized conductors out of the way. He pushed them against a 152-mm-deep, 305-mm by 305-mm, metal electrical box, and the edge of the box pierced the electrical tape covering a splice on one of the energized conductors. (The employee had believed that the tape was sufficient protection.) The resulting electrical fault caused an electric arc that burned the electrician's body. He was hospitalized for his injuries.

Keywords: BURN, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL BOX, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119605582 Hospitalized injury Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close