Inspection Detail
Inspection: 119544690 - Bartley & Devary Electric, Inc. T/A B&D Electric
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address:
Bartley & Devary Electric, Inc. T/A B&D Electric
115 East Northpoint Drive
Salisbury, MD 21801
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/08/1998
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 01/29/1999
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100964337 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $687 | $0 | $0 | $0 | $0 | $687 |
| Current Penalty | $200 | $0 | $0 | $0 | $0 | $200 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 09122303 A | 11/23/1998 | 11/27/1998 | $200 | $687 | $0 | I - Informal Settlement |
Investigation Summary
An electrician was installing the neutral conductor for an emergency lighting system onto the neutral bus of an 800-ampere cabinet. An 800-ampere, three-phase main circuit breaker, which had been previously installed in the cabinet, was open. However, the conductors feeding this circuit breaker were energized. Because an excessive amount of insulation had been stripped from the six conductors that were connected to the circuit breaker, about 20 millimeters of conductor was exposed on each of the six conductors. As the electrician was routing the neutral conductor behind other conductors in the cabinet, an electrical fault occurred. The ensuing electric arc burned the employee on both hands. He was hospitalized for his injuries. Representatives of the company believed that the neutral conductor contacted the exposed portion of one of the supply conductors. However, there was no evidence of burning or damage to the neutral conductor.
Keywords: BURN, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, E C, ELECTRIC CONDUCTOR, ELECTRICAL CABINET, ELECTRICAL FAULT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 119544690 | Hospitalized injury | Burn/Scald(Heat) | Electricians |