Powered by GoogleTranslate

Inspection Detail

Inspection: 119526960 - Dpw-Bureau Of Transportation, Maintenace Watershed

Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 119526960
Report ID: 0352450
Date Opened: 12/05/1994

Site Address:
Dpw-Bureau Of Transportation, Maintenace Watershed
5865 Oakland Road
Sykesville, MD 21784

Mailing Address:
23-25 South Gay Street, Baltimore, MD 21202

Union Status: Union

SIC:9511

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 12/13/1994

Emphasis: L:9311

Case Closed: 05/05/1995


Related Activity
Type Activity Nr Safety Health
Accident 361018013
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100147 C01 01/25/1995 01/27/1995 $0 $0 $0 -  
2. 02001 Serious 19100303 F 01/25/1995 01/27/1995 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 891432
Event: 11/28/1994
BURN - ELECTRICAL FAULT IN FUSE BLOCK

A couple of weeks before the accident, some employees had tried to start up a saw mill. However, they could not get the dust chains to operate. The problem appeared to be electrical in nature, so the street lighting section was notified. On the day of the accident, a three-person crew (an electrical supervisor, an electrician, and a helper) arrived to find and repair the problem. To correct the problem, they started working on a 480-volt, 400-ampere panelboard. They had opened the top fuse on the panelboard, which they thought was the main disconnect. However, this fuse, which was not properly identified, only controlled the circuit to the head saw. The supervisor started switching fuses from one 30-ampere fuse block, which the crew thought was faulty, to another, spare, block. Each of the fuse blocks was equipped with a switch to deenergize the fuse block when the panel door was open. Therefore, when the supervisor tested the fuse block containing the fuses to be moved, he found it to be deenergized. Unfortunately, the interlock switch for the spare fuse block was faulty, and the spare fuse block remained energized. He had switched the lead conductors and was transferring the fuse terminals when his screwdriver contacted an energized screw. This caused an electrical fault, and the ensuing electric arc burned the supervisor. He sustained second degree burns to both hands and first degree burns to his face. He was hospitalized for his injuries.

Keywords: BURN, FUSE, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 119526960 Hospitalized injury Burn/Scald(Heat) Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.