Inspection Detail
Inspection: 1162911.015 - A & R Consulting, Llc
Inspection Information - Office: Nv-E-Las Vegas 0953220
Site Address:
A & R Consulting, Llc
3516 Wynn Road
Las Vegas, NV 89103
Mailing Address:
752 Feather Ridge Drive, Henderson, NV 89052
Union Status: NonUnion
SIC:
NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors
Inspection Type: Fat/Cat
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/15/2016
Emphasis: S:Elut
Case Closed: 12/13/2016
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 1109398 | Yes | |
| Inspection | 1164120 | Yes | |
| Inspection | 1164131 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 1 | 4 | |||
| Current Violations | 3 | 1 | 4 | |||
| Initial Penalty | $4,500 | $0 | $0 | $300 | $0 | $4,800 |
| Current Penalty | $3,600 | $0 | $0 | $240 | $0 | $3,840 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100333 A | 08/25/2016 | 08/31/2016 | $1,200 | $1,500 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100333 B02 V D | 08/25/2016 | 08/31/2016 | $1,200 | $1,500 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19100335 A01 I | 08/25/2016 | 08/31/2016 | $1,200 | $1,500 | $0 | I - Informal Settlement | ||
| 4. | 02001 | Other | NEVADA REVISED STATUTES 618.378(1 | 08/25/2016 | 08/31/2016 | $240 | $300 | $0 | I - Informal Settlement |
Investigation Summary
On July 14, 2016, an employee was working for a plumbing, heating, and air conditioning contractor. He was sealing air ducts to prevent leakage. A coworker was ready to reenergize an air conditioning unit after its installation. The coworker yelled clear! As he stood up, the employee grabbed a side of the air conditioner. That side had an open panel. The employee sustained an electric shock. The current entered his left hand and exited his right knee. His right knee was in contact with a metal pipe. The employee was resuscitated at the scene. He was taken to a hospital, where he was placed in a medically induced coma. The employee was hospitalized for thirteen days before dying. He never awakened.
Keywords: Air Conditioner, E GI IV (no lockout), Elec Circ Part--Misc, Electric Shock, Electrical, Electrical Work, Electrician, Electrocuted, Lockout/Tagout
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1162911.015 | 26 | M | Fatality | Helpers, construction trades |
Translate