Inspection Detail
Inspection: 116150061 - Connecticut Light & Power Company
Inspection Information - Office: Hartford
Site Address:
Connecticut Light & Power Company
Route 87
Lebanon, CT 06249
Mailing Address:
107 Selden Street, Berlin, CT 06037
Union Status: Union
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/21/2001
Emphasis:
Case Closed: 07/09/2001
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 100080159 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $10,000 | $0 | $0 | $0 | $0 | $10,000 |
Current Penalty | $10,000 | $0 | $0 | $0 | $0 | $10,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19100269 A02 IIA | 03/26/2001 | 06/10/2001 | $5,000 | $5,000 | $0 | I - Informal Settlement | ||
2. | 01001B | Serious | 19100269 A03 | 03/26/2001 | 05/10/2001 | $0 | $0 | $0 | I - Informal Settlement | Citation has been deleted. | |
3. | 01001C | Serious | 19100269 C | 03/26/2001 | 05/10/2001 | $0 | $0 | $0 | I - Informal Settlement | Citation has been deleted. | |
4. | 01002 | Serious | 19100269 N03 | 03/26/2001 | 06/10/2001 | $5,000 | $5,000 | $0 | I - Informal Settlement |
Investigation Summary
A power line crew was repairing a storm-damaged utility pole and a 345-kilovolt overhead power line supported by the pole. The power line was deenergized and grounded. The line conductors were bonded together and grounded to a pole ground. There were two static wires supported by the structure, but they were not grounded or bonded. The employees moved the static wire from the damaged pole to an adjacent center pole. After the crew moved the static wire, two employees went up in an aerial lift to the center pole to connect the static wire to a fitting on the pole. One of employees removed his leather work gloves and grabbed the static wire. He was electrocuted.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 116150061 | Fatality | Electric Shock | Electrical power installers and repairers |