Powered by GoogleTranslate

Inspection Detail

Inspection: 1159128 - Steel Systems Inc

Inspection Information - Office: Birmingham Area Office

 

Inspection Nr: 1159128
Report ID: 0418300
Date Opened: 05/29/1984

Site Address:
Steel Systems Inc
401 Taylor St
Scottsboro, AL 35768

Mailing Address:
P O Box 149, Decatur, AL 35602

Union Status: NonUnion

SIC:1791

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 05/30/1984

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 03/16/2016


Related Activity
Type Activity Nr Safety Health
Accident 360537450
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $350 $0 $0 $0 $0 $350
Current Penalty $245 $0 $0 $0 $0 $245
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260550 A15 I 06/12/1984 06/15/1984 $245 $350 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 14350110
Event: 05/24/1984
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CRANE

ON A CONSTRUCTION SITE AT AN OCCUPIED MANUFACTURING PLANT, A PITMAN HYDRA-LIFT TRUCK CRANE WAS BEING USED TO MOVE STRUCTURAL STEEL FROM A STORAGE AREA TO THE SLAB FOR THE PLANT ADDITION. A 34-FOOT-LONG STEEL TRUSS WAS HOISTED FOR PLACEMENT ONTO THE FLATBED OF THE TRUCK CRANE. TWO WORKERS HELD THE TRUSS (ONE AT EACH END) TO STEADY IT AND TO GUIDE IT ONTO THE TRUCK. WHEN THE CRANE OPERATOR ANGLED THE BOOM UPWARDS, IT CONTACTED A 7200-VOLT OVERHEAD POWER LINE, WHICH WAS 23 FEET ABOVE THE GROUND. THE TWO WORKERS HOLDING ONTO THE STEEL TRUSS WERE ELECTROCUTED. THE GRASS AROUND THE TWO OUTRIGGERS CAUGHT FIRE, BUT THE CRANE OPERATOR WAS NOT INJURED. PERSONS ON THE SITE WERE NOT TRAINED CONCERING THE REQUIRED SAFE CLEARANCE DISTANCES.

Keywords: ERECTION PROCESS, OVERHEAD POWER LINE, ELECTRICAL, E C, BOOM, CRANE BOOM, ELECTROCUTED, CONSTRUCTION, STEEL ERECTION, CRANE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1159128 Fatality Electric Shock Occupation not reported
2 1159128 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close