Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 115705394 - Norpac Foods Inc

Inspection Information - Office: Or Safety 2-Salem

 

Inspection Nr: 115705394
Report ID: 1054113
Open Date: 12/27/1991

Site Address:
Norpac Foods Inc
930 W Washington St
Stayton, OR 97383

Mailing Address:
Po Box 458, Stayton, OR 97383

Union Status: Union

SIC:2037

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/20/1992

Planning Guide: Safety-Manufacturing

Emphasis:

Close Case:06/03/1992


Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $3,500 $0 $0 $0 $0 $3,500
Current Penalty $3,500 $0 $0 $0 $0 $3,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A01 03/09/1992 01/06/1992 $2,500 $2,500 $0 -  
2. 01002 Serious 19100335 A01 V 03/09/1992 01/06/1992 $500 $500 $0 -  
3. 01003 Serious 740003002 C 03/09/1992 01/06/1992 $500 $500 $0 -  

Investigation Summary

Investigation Nr: 170129241
Event: 12/27/1991
Burn - Electrical Fault In Switchboard

A JOURNEYMAN ELECTRICIAN FOR A CANNERY WAS REPLACING A 480-VOLT FUSE IN A SWITCHBOARD LOCATED IN A COMPUTER CONTROL ROOM. THE CIRCUIT WAS ENERGIZED AT THE TIME. A SECOND EMPLOYEE WAS STANDING NEARBY, OBSERVING THE WORK, WHILE TWO MORE EMPLOYEES ATTENDED THE ROPE THAT WAS TIED AROUND THE ELECTRICIAN. THE ELECTRICIAN WAS USING A FUSE PULLER TO PULL THE FUSE, AND HE HAD A LENGTH OF INSULATED METAL THAT WAS BEING USED AS A JUMPER TO BYPASS THE FUSE AND COMPLETE THE CIRCUIT. THE ELECTRICIAN WAS ALSO WEARING RUBBER INSULATING GLOVES. AS THE FUSE BEGAN TO LOOSEN, AN ELECTRIC ARC OCCURRED BURNING THREE OF THE EMPLOYEES. THE ELECTRICIAN (EMPLOYEE #1) RECEIVED FIRST DEGREE BURNS ON HIS HANDS, FACE, AND NECK. THE OBSERVER (EMPLOYEE #2) RECEIVED FIRST DEGREE BURNS ON HIS FACE. ONE OF THE OTHER TWO EMPLOYEES RECEIVED A FIRST DEGREE BURN ON HIS ARM. THE ELECTRICIAN WAS HOSPITALIZED FOR ONE WEEK FOR HIS INJURIES. THE OBSERVER WAS TREATED ON AN OUT-PATIENT BASIS, AND THE THIRD INJURED EMPLOYEE WAS NOT TREATED FOR HIS INJURIES.

Keywords:burn, clothing, fuse, electric arc, e gi iii, electrical, switchboard, lockout, electrical fault

Investigated Inspection
# Inspection Age Sex Degree Nature Occupation
1 115705394 Non Hospitalized injury Burn/Scald(Heat) Managers and administrators, n.e.c
2 115705394 Non Hospitalized injury Burn/Scald(Heat) Not specified mechanics and repairers
3 115705394 Hospitalized injury Burn/Scald(Heat) Electronic repairers, communica. & indus. equip.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.