Inspection Detail
Inspection: 115692907 - Idaho Power Company
Inspection Information - Office: Bend
Site Address:
Idaho Power Company
Halfway Substation
Halfway, OR 97834
Mailing Address:
Po Box 70, Boise, ID 87307
Union Status: NonUnion
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/19/1992
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 05/20/1993
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361529449 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 12 | 1 | 13 | |||
| Current Violations | 7 | 7 | ||||
| Initial Penalty | $30,000 | $10,000 | $0 | $0 | $0 | $40,000 |
| Current Penalty | $17,500 | $0 | $0 | $0 | $0 | $17,500 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 7030820 | 03/24/1992 | 03/27/1992 | $2,500 | $2,500 | $0 | 04/10/1992 | L - State Settlement | |
| 2. | 01002 | Serious | 19260957 A02 I | 03/24/1992 | 03/27/1992 | $0 | $2,500 | $0 | 04/10/1992 | L - State Settlement | Citation has been deleted. |
| 3. | 01003 | Serious | 19260957 A02 II | 03/24/1992 | 03/27/1992 | $2,500 | $2,500 | $0 | 04/10/1992 | L - State Settlement | |
| 4. | 01004 | Serious | 19260950 B02 | 03/24/1992 | 03/27/1992 | $2,500 | $2,500 | $0 | 04/10/1992 | L - State Settlement | |
| 5. | 01005 | Serious | 19260951 C01 | 03/24/1992 | 03/27/1992 | $0 | $2,500 | $0 | 04/10/1992 | L - State Settlement | Citation has been deleted. |
| 6. | 01006 | Serious | 19260957 C01 | 03/24/1992 | 03/27/1992 | $0 | $2,500 | $0 | 04/10/1992 | L - State Settlement | Citation has been deleted. |
| 7. | 01007 | Serious | 7030115 | 03/24/1992 | 03/27/1992 | $2,500 | $2,500 | $0 | 04/10/1992 | L - State Settlement | |
| 8. | 01008 | Serious | 7030130 | 03/24/1992 | 03/27/1992 | $0 | $2,500 | $0 | 04/10/1992 | L - State Settlement | Citation has been deleted. |
| 9. | 01009 | Serious | 19260950 C01 | 03/24/1992 | 03/27/1992 | $2,500 | $2,500 | $0 | 04/10/1992 | L - State Settlement | |
| 10. | 01010 | Serious | 7030305 | 03/24/1992 | 03/27/1992 | $0 | $2,500 | $0 | 04/10/1992 | L - State Settlement | Citation has been deleted. |
| 11. | 01011 | Serious | 19260957 A01 | 03/24/1992 | 03/27/1992 | $2,500 | $2,500 | $0 | 04/10/1992 | L - State Settlement | |
| 12. | 01012 | Serious | 740003002 C | 03/24/1992 | 03/27/1992 | $2,500 | $2,500 | $0 | 04/10/1992 | L - State Settlement | |
| 13. | 02013 | Willful | 740003001 | 03/24/1992 | 03/27/1992 | $0 | $10,000 | $0 | 04/10/1992 | L - State Settlement | Citation has been deleted. |
Investigation Summary
A POWER LINE WORKER WAS INTERCHANGING TWO SETS OF THREE-PHASE 7200-VOLT UNDERGROUND CONDUCTORS BETWEEN TWO TRANSFORMERS. THE EMPLOYEE HAD OPENED ALL SIX LOAD BREAK CUTOUTS AND HAD GROUNDED THE LOW-VOLTAGE SIDE USING A LIVE-LINE TOOL. AS HE WAS WORKING ON THE LAST CONNECTION OF THE FIRST SET, THE EMPLOYEE CONTACTED THE HIGH-VOLTAGE SIDE CUTOUT WITH HIS LEFT HAND. THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK. BURN MARKS WERE FOUND ON HIS RIGHT HEEL AND ON THE FIFTH STEP OF THE LADDER, WHERE HE WAS STANDING. CARDIO-PULMONARY RESUSCITATION WAS APPLIED, AND DEFIBRILLATION WAS ATTEMPTED TO NO AVAIL. THE EMPLOYEE WAS ELECTROCUTED.
Keywords: PROTECTIVE GROUNDING, ELECTRICAL, CPR, POWER LINE WORKER, ELECTRIC CABLE, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UNDRGRD POWER LINE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 115692907 | Fatality | Electric Shock | Supervisors; electricians & power transm. install. |
Translate