Powered by GoogleTranslate

Inspection Detail

Inspection: 115682825 - Sumter Builders, Inc.

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 115682825
Report ID: 0454510
Date Opened: 01/23/1992

Site Address:
Sumter Builders, Inc.
Hwy. 23 S.
Batesburg, SC 29006

Mailing Address:
P. O. Box 579, Sumter, SC 29151

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/13/1992

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 03/15/1992


Related Activity
Type Activity Nr Safety Health
Accident 360496905
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $8,000 $0 $0 $0 $0 $8,000
Current Penalty $3,200 $0 $0 $0 $0 $3,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 02001 Serious 19260950 B01 02/24/1992 02/27/1992 $1,600 $4,000 $0 I - Informal Settlement  
2. 02002 Serious 19260950 D01 IV 02/24/1992 02/27/1992 $1,600 $4,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 910430
Event: 01/21/1992
ELECTRIC SHOCK - CONTACT WITH OVERHEAD STATIC LINE

A POWER LINE CONTRACTOR CREW WAS REPLACING A 60-FOOT CLASS 2 UTILITY POLE, CROSSARMS, AND HARDWARE ON A DEENERGIZED 69-KILOVOLT OVERHEAD POWER LINE. THE EMPLOYEES HAD ALMOST COMPLETED THE JOB. THEY ONLY HAD TO ATTACH ONE CROSSARM BRACKET TO THE NEW POLE. THE OLD POLE WAS TOO CLOSE TO ALLOW THE EMPLOYEES TO DRILL THE HOLES, SO THE EMPLOYEES HAD TO REMOVE IT FIRST. ONE OF THE EMPLOYEES, WHO WAS WORKING OUT OF AN AERIAL LIFT, WAS ATTACHING A HAND LINE TO THE TOP OF THE OLD POLE. TO DO THIS, HE LEANED AGAINST THE STATIC LINE, REACHED AROUND BOTH POLES, AND TOUCHED EITHER THE NEW STATIC BRACKET OR THE NEW POLE'S GROUND WIRE. A 3- TO 5-FOOT SECTION OF THE GROUND WIRE ON THE OLD POLE WAS MISSING, AND THE STATIC LINE HAD NOT BEEN GROUNDED TO THE DEENERGIZED PHASE CONDUCTORS. (THE EMPLOYEES HAD NOT INSPECTED THE CONDITION OF THE OLD POLE BEFORE PERFORMING THE JOB.) THE EMPLOYEE IN THE AERIAL LIFT WAS ELECTROCUTED BY THE DIFFERENCE IN POTENTIAL BETWEEN THE EXISTING STATIC WIRE AND THE NEW GROUND WIRE.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, POTENTIAL GRADIENT, ELECTROCUTED, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 115682825 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.