Powered by GoogleTranslate

Inspection Detail

Inspection: 115669517 - Sumter Builders

Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation

 

Inspection Nr: 115669517
Report ID: 0454510
Date Opened: 08/06/1991

Site Address:
Sumter Builders
Berkeley Rd.
Leesville, SC 29070

Mailing Address:
P. O. Box 579, Sumter, SC 29151

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/19/1991

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/16/1991


Related Activity
Type Activity Nr Safety Health
Accident 360496731
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $1,290 $0 $0 $0 $0 $1,290
Current Penalty $1,290 $0 $0 $0 $0 $1,290
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260955 C03 09/04/1991 09/07/1991 $800 $800 $0 -  
2. 01002 Serious 19260955 C05 09/04/1991 09/09/1991 $490 $490 $0 -  

Investigation Summary

Investigation Nr: 908327
Event: 08/05/1991
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CONDUCTOR

A CREW OF EMPLOYEES WAS STRINGING NEW OVERHEAD CONDUCTORS FOR A POWER LINE. TWO OF THE EMPLOYEES WERE BEHIND A SPOOL TRAILER, WATCHING THE CONDUCTOR AS IT WAS PULLED FROM THE OTHER END, ABOUT 0.5 MILES AWAY, BY TWO OTHER EMPLOYEES. THE TWO SETS OF EMPLOYEES WERE IN RADIO CONTACT DURING THE STRINGING OPERATION. OCCASIONALLY, THE CONDUCTOR BEING PULLED WOULD BOUNCE BECAUSE OF THE PULLING ROPE GOING THROUGH THE SHEAVES AND BECAUSE OF AN OCCASIONAL LAP ON THE CONDUCTOR SPOOLS. THE TWO EMPLOYEES AT THE SPOOL TRAILER HEARD ARCING, AND ONE OF THEM STEPPED TO THE RIGHT SIDE OF THE TRAILER TO LOOK DOWN THE LINE. WHEN HE TURNED AROUND, THE OTHER EMPLOYEE WAS LYING ON THE GROUND TO THE LEFT OF THE REAR END OF THE TRAILER. ALTHOUGH THE TRAILER WAS GROUNDED TO A GUY AT A POLE AND THE CONDUCTOR BEING STRUNG WAS GROUNDED TO THE TRAILER, THERE WAS STILL ENOUGH OF A POTENTIAL GRADIENT TO ELECTROCUTE THE EMPLOYEE AS THE CONDUCTOR BEING STRUNG APPARENTLY CONTACTED AN EXISTING ENERGIZED CONDUCTOR.

Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 115669517 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close