Inspection: 115512030 - Sea-Land Corporation
Inspection Information - Office: Dosh Seattle Service Location, Seattle, Wa
Site Address:
Sea-Land Corporation
206 Sw Michigan St
Seattle, WA 98106
Mailing Address:
1601-5th Ave Suite 2100, Seattle, WA 98101
Union Status: Union
SIC:8741
NAICS: 0
Inspection Type: Unprog Rel
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/17/1991
Emphasis:
Case Closed: 10/17/1991
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361192248 |
Investigation Summary
AN EMPLOYEE WAS DELIVERING A REFRIGERATED CONTAINER TO A SEAFOOD PROCESSING AND COLD STORAGE WAREHOUSE. HE PLUGGED THE POWER SUPPLY CORD FROM THE CONTAINER INTO A CORD CONNECTOR ON THE DELIVERY DOCK. THE CORD CONNECTOR WAS BROKEN, ALLOWING THE SLOTS TO ROTATE. THE EMPLOYEE CONNECTED THE PLUG SO THAT THE GROUNDING BLADE WAS CONNECTED TO ONE OF THE CIRCUIT CONDUCTORS, WHICH ENERGIZED THE TRAILER. THE EMPLOYEE WAS ELECTROCUTED.
Keywords: ELECTRICAL, ATTACHMENT PLUG, GROUND FAULT, CORD CONNECTOR, EQUIPMENT GROUNDING, E GI V, ELECTROCUTED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 115512030 | Occupation Not Listed |