Inspection Detail
Inspection: 115444085 - D W Close Co Inc
Inspection Information - Office: Dosh Everett Service Location, Everett, Wa
Site Address:
D W Close Co Inc
3303 W Casino Rd
Everett, WA 98203
Mailing Address:
Po Box 24246, Seattle, WA 98124
Union Status: Union
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 04/21/1995
Emphasis:
Case Closed: 02/10/1998
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361235047 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $14,400 | $0 | $0 | $0 | $0 | $14,400 |
| Current Penalty | $4,800 | $0 | $0 | $0 | $0 | $4,800 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 1550042801 D | 05/02/1995 | 04/21/1995 | $4,800 | $4,800 | $0 | 05/10/1995 | F - Formal Settlement | Citation has been deleted. |
| 2. | 01001B | Serious | 1550042904 D 02 | 05/02/1995 | 04/21/1995 | $0 | $0 | $0 | 05/10/1995 | F - Formal Settlement | Citation has been deleted. |
| 3. | 01002 | Serious | 1550042801 A | 05/02/1995 | 04/21/1995 | $4,800 | $4,800 | $0 | 05/10/1995 | F - Formal Settlement | Citation has been deleted. |
| 4. | 01003A | Serious | 1550010001 B | 05/02/1995 | 05/19/1995 | $4,800 | $4,800 | $0 | 05/10/1995 | F - Formal Settlement | |
| 5. | 01003B | Other | 1550010001 C | 05/02/1995 | 06/04/1995 | $0 | $0 | $0 | 05/10/1995 | F - Formal Settlement |
Investigation Summary
An electrician and his apprentice were replacing 277-volt conductors supplying an overhead light for a building. (The wiring had been damaged during construction.) The apprentice was in an aerial lift. The electrician had climbed out of the aerial lift and was lying on his back atop an overhead unpainted vent that was about 4.9 meters (16 feet) above the floor. He was going to cut and cap one of the conductors, which remained energized. The apprentice saw the conductor in the jaws of the side-cutting pliers the electrician was holding. When the pliers cut into the conductor, the electrician was electrocuted.
Keywords: E GI IV, ELECTRICAL, INSULATED TOOL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 115444085 | Fatality | Electric Shock | Electricians |
Translate