Inspection Detail
Inspection: 115430274 - Cascade Electric Services Inc
Inspection Information - Office: Dosh Spokane Service Location, Spokane, Wa
Site Address:
Cascade Electric Services Inc
1034 6th Ave N
Kent, WA 98032
Mailing Address:
12414 Hwy 99 S Ste 105, Everett, WA 98204
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/24/1993
Emphasis:
Case Closed: 03/21/1994
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 361194335 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | 2 | |||
Current Violations | 1 | 1 | ||||
Initial Penalty | $1,350 | $0 | $0 | $0 | $0 | $1,350 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 0240097502 B 04B | 12/01/1993 | 09/24/1993 | $1,350 | $1,350 | $0 | 01/18/1994 | Y - State Decision | Citation has been deleted. |
2. | 02001 | Other | 0240004001 A | 12/01/1993 | 01/03/1994 | $0 | $0 | $0 | 01/18/1994 | Y - State Decision |
Investigation Summary
An employee was tracing a secondary circuit that had a fault. He had checked a secondary junction box and found a failed elbow. He then moved to a three-phase, pad-mounted transformer. He discovered an open fuse on the 7200-volt primary side of the transformer. He decided to test the fuse with a low-voltage voltmeter. The voltmeter failed, and the employee sustained burns on his hands, face, and right arm from the ensuing electric arc. The employee, who was not qualified to work on the high voltage side of the transformer, was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, TEST EQUIPMENT, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT, TRANSFORMER, UNTRAINED
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 115430274 | Hospitalized injury | Electric Shock | Electricians |