Powered by GoogleTranslate

Inspection Detail

Inspection: 115415960 - Evergreen Utilities Contractors Inc

Inspection Information - Office: Dosh Seattle Service Location, Seattle, Wa

 

Inspection Nr: 115415960
Report ID: 1055320
Date Opened: 07/31/1996

Site Address:
Evergreen Utilities Contractors Inc
5 Miles N Of Entiat Wa On The W Side Of Hwy 97a
Entiat, WA 98822

Mailing Address:
Po Box 686, Woodinville, WA 98072

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/05/1996

Emphasis: L:Wasafety

Case Closed: 12/24/1997


Related Activity
Type Activity Nr Safety Health
Accident 361208721
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 2 2 10
Current Violations 3 1 1 5
Initial Penalty $26,600 $0 $13,600 $0 $0 $40,200
Current Penalty $4,250 $0 $2,000 $0 $0 $6,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Repeat 0456502707 12/16/1996 11/05/1996 $11,200 $11,200 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
2. 01002 Repeat 0456504115 12/16/1996 11/05/1996 $2,000 $2,400 $0 12/20/1996 F - Formal Settlement  
3. 02001A Serious 0456502602 A 12/16/1996 11/05/1996 $1,000 $5,600 $0 12/20/1996 F - Formal Settlement  
4. 02001B Serious 0456502602 D 12/16/1996 11/05/1996 $0 $0 $0 12/20/1996 F - Formal Settlement  
5. 02001C Serious 0456502603 A 05/29/1997 11/05/1996 $0 $0 $0 F - Formal Settlement  
6. 02002A Serious 0456502603 A 12/16/1996 11/05/1996 $5,600 $5,600 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
7. 02002B Serious 0456502603 D 12/16/1996 11/05/1996 $0 $0 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
8. 02002C Serious 0456500901 12/16/1996 11/05/1996 $0 $0 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
9. 02003A Serious 0456502705 A 12/16/1996 11/05/1996 $5,600 $5,600 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
10. 02003B Serious 0456500904 12/16/1996 11/05/1996 $2,250 $0 $0 12/20/1996 F - Formal Settlement  
11. 02004A Serious 0456504114 12/16/1996 11/05/1996 $5,600 $5,600 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
12. 02004B Serious 0456504130 12/16/1996 11/05/1996 $0 $0 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
13. 02005 Serious 0456500906 12/16/1996 11/05/1996 $3,200 $3,200 $0 12/20/1996 F - Formal Settlement Citation has been deleted.
14. 02006A Serious 0456504114 05/29/1997 11/05/1996 $1,000 $1,000 $0 F - Formal Settlement  
15. 02006B Serious 0456504130 05/29/1997 11/05/1997 $0 $0 $0 F - Formal Settlement  
16. 02006C Serious 0456504140 05/29/1997 11/05/1996 $0 $0 $0 F - Formal Settlement  
17. 03001 Other 0456500903 12/16/1996 11/05/1996 $0 $0 $0 12/20/1996 F - Formal Settlement  
18. 03002 Other 0456504140 12/16/1996 11/05/1996 $0 $0 $0 12/20/1996 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 170100333
Event: 07/30/1996
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU CONDUCTOR

Three employees were working from a Condor 90 uninsulated aerial lift to move the three phase conductors of an existing overhead power line so that a stringing operation could continue. The existing line was deenergized, but was not grounded. A 7200-volt overhead power line was located below the deenergized line. The employees had not covered the energized line or otherwise protected it against contact. When the employees got into position to work, two of them put one of the deenergized conductors on their shoulders, lifted it over the end of the arm of the wishbone structure, and began to lower it to the lower arm. As the employees were lowering the conductor, it contacted the energized line at mid span. The two employees received electric shocks and were hospitalized for their injuries.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 115415960 Hospitalized injury Electric Shock Electrical power installers and repairers
2 115415960 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.