Related Activity
Type Activity Nr Safety Health
Accident 361311129
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 2 7
Current Violations 4 3 7
Initial Penalty $22,000 $0 $0 $0 $0 $22,000
Current Penalty $12,625 $0 $0 $0 $0 $12,625
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B01 12/22/1993 01/09/1994 $3,750 $5,000 $0 I - Informal Settlement  
2. 01002 Serious 19100303 H03 12/22/1993 01/09/1994 $2,625 $3,500 $0 I - Informal Settlement  
3. 01003A Serious 19100333 A01 12/22/1993 01/09/1994 $3,750 $5,000 $0 I - Informal Settlement  
4. 01003B Serious 19100333 B02 IIIA 12/22/1993 01/09/1994 $0 $0 $0 I - Informal Settlement  
5. 01004 Serious 19100335 A01 I 12/22/1993 01/09/1994 $2,500 $5,000 $0 I - Informal Settlement  
6. 01005 Other 19100335 A01 II 12/22/1993 01/09/1994 $0 $3,500 $0 I - Informal Settlement  
7. 02001 Other 19100147 C04 I 12/22/1993 01/09/1994 $0 $0 $0 -  
8. 02002 Other 19100332 B01 12/22/1993 01/09/1994 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 170105464
Event: 10/09/1993
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN ELECTRICIAN WAS REPLACING A 6900-VOLT AC CONTACTOR FOR AN INDUCTION HEATER ON A BAR MILL. THE CABINET ON WHICH THE EMPLOYEE WAS WORKING WAS LOCATED ON A METAL PLATFORM THAT WAS ATTACHED TO THE FRAME OF THE BUILDING. THE BUILDING'S STRUCTURE WAS USED AS A GROUNDING ELECTRODE; THUS, THE PLATFORM WAS AT GROUND POTENTIAL. THE 6900-VOLT POWER SUPPLY TO THE CABINET HAD NOT BEEN DEENERGIZED BEFORE THE EMPLOYEE BEGAN HIS WORK. AFTER THE NEW CONTACTOR HAD BEEN SLID INTO PLACE AND LOCKED DOWN, THE ELECTRICIAN REACHED INTO THE LEFT SIDE OF THE CABINET TO RETRIEVE A 120-VOLT CONTROL VOLTAGE PLUG TO COMPLETE THE INSTALLATION. AS HE DID SO, HE CONTACTED AN ENERGIZED SURGE COIL. HE RECEIVED AN ELECTRIC SHOCK AND WAS TRANSPORTED TO A HOSPITAL. HE DIED OF ELECTROCUTION AT 3:10 PM THAT SAME DAY.

Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL CABINET

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 114988918 Fatality Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close