Powered by GoogleTranslate

Inspection Detail

Inspection: 114571458 - Las Vegas Electric, Inc.

Inspection Information - Office: Nv-E-Las Vegas 0953220

 

Inspection Nr: 114571458
Report ID: 0953220
Date Opened: 06/30/1992

Site Address:
Las Vegas Electric, Inc.
41 North Mojave Road
Las Vegas, NV 89110

Mailing Address:
3305 Meade Avenue, Las Vegas, NV 89102

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/28/1992

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/18/1992


Related Activity
Type Activity Nr Safety Health
Accident 360591952
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,500 $0 $0 $0 $0 $1,500
Current Penalty $750 $0 $0 $0 $0 $750
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A03 08/14/1992 08/17/1992 $750 $1,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 969006
Event: 06/28/1992
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

AN ELECTRICIAN WAS PULLING AN ELECTRICAL SERVICE INTO A 2000-AMPERE, 480-VOLT MAIN SERVICE PANELBOARD. THE EMPLOYER SCHEDULED THE WORK ON A SUNDAY BECAUSE THE FACILITY WAS A FOOD STORAGE AND PROCESSING PLANT, WHICH WOULD BE LEAST AFFECTED BY A POWER OUTAGE ON A NON-WORKDAY. THE COMPANY'S SENIOR OFFICER, WHO WAS ASSISTING AS WELL AS SUPERVISING, ATTEMPTED TO DEENERGIZE THE SYSTEM BY OPENING THE MAIN DISCONNECT. THIS ACTION, HOWEVER, ONLY DEENERGIZED THE LOAD SIDE OF THE CIRCUIT, AND THE SERVICE ENTRANCE CONDUCTORS WERE STILL ENERGIZED. THE SUPERVISOR INSTRUCTED THE CREW TO TEST THE CIRCUITS BEFORE BEGINNING WORK. ANOTHER EMPLOYEE OPENED A SUB-PANEL, TESTED IT, AND FOUND IT TO BE DEENERGIZED. HE RELAYED THIS INFORMATION TO THE OTHER CREW MEMBERS. SOON AFTER THIS, THE SUPERVISOR AND ANOTHER EMPLOYEE NOTICED THE ELECTRICIAN SLUMPED OVER AT HIS WORK AREA (THE MAIN PANELBOARD). THE ELECTRICIAN WAS BLEEDING FROM HIS HEAD AND WAS NOT BREATHING. HE DIED OF ELECTROCUTION A SHORT TIME LATER. AFTER THE ACCIDENT, A CHECK FOUND AN ENERGIZED LINE WITHIN THE ELECTRICIAN'S WORK AREA. IT WAS THE 480-VOLT (277-VOLT-TO-GROUND) SERVICE ENTRANCE CONDUCTORS FOR THE MAIN CIRCUIT BREAKER, AND IT ORIGINATED AT THE ELECTRIC UTILITY'S TRANSFORMER. THE TERMINAL LUGS AND BUSES TO WHICH THESE CONDUCTORS WERE CONNECTED WERE ALSO ENERGIZED.

Keywords: E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 114571458 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.