Powered by GoogleTranslate

Inspection Detail

Inspection: 114125891 - Empire Cheese Inc.

Inspection Information - Office: Buffalo Area Office

 

Inspection Nr: 114125891
Report ID: 0213600
Date Opened: 08/25/1998

Site Address:
Empire Cheese Inc.
4520 Haskell Road
Cuba, NY 14727

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:2022

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/11/1998

Emphasis:

Case Closed: 01/28/1999


Related Activity
Type Activity Nr Safety Health
Accident 101330157
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 1 7
Current Violations 6 1 7
Initial Penalty $15,750 $0 $0 $0 $0 $15,750
Current Penalty $11,025 $0 $0 $0 $0 $11,025
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100023 C01 12/16/1998 12/21/1998 $1,225 $1,750 $0 I - Informal Settlement  
2. 01002 Serious 19100303 B01 12/16/1998 01/04/1999 $2,450 $3,500 $0 I - Informal Settlement  
3. 01003 Serious 19100304 E01 I 12/16/1998 01/04/1999 $1,225 $1,750 $0 I - Informal Settlement  
4. 01004 Serious 19100304 F04 12/16/1998 01/04/1999 $2,450 $3,500 $0 I - Informal Settlement  
5. 01005 Serious 19100304 F05 V 12/16/1998 12/21/1998 $1,225 $1,750 $0 I - Informal Settlement  
6. 01006 Serious 19100305 A01 I 12/16/1998 01/04/1999 $2,450 $3,500 $0 I - Informal Settlement  
7. 02001 Other 19100106 D02 I 12/16/1998 12/21/1998 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 638833
Event: 08/24/1998
ELECTRIC SHOCK - GROUND FAULT IN CONDUIT

An employee was changing a filter on an ultraviolet liquid-purifying machine. The machine was used to kill bacteria in a circulating brine solution in a cheese manufacturing plant. Standing on a wet floor, the employee contacted a stainless steel conduit. The conduit was not effectively grounded, and a ground fault caused by a conductor with defective insulation energized the conduit to 650 volts. The employee was electrocuted.

Keywords: ELEC INSULATION, ELECTRICAL, CONDUIT, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 114125891 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close