Powered by GoogleTranslate

Inspection Detail

Inspection: 112397591 - The Scherr Companies

Inspection Information - Office: Va-E-Richmond (Regional Office) - Safety 0355111

 

Inspection Nr: 112397591
Report ID: 0355111
Date Opened: 08/20/1991

Site Address:
The Scherr Companies
2343 W. Broad Street
Richmond, VA 23220

Mailing Address:
2256-C Dabney Raod, Richmond, VA 23230

Union Status: NonUnion

SIC:7623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/22/1991

Emphasis:

Case Closed: 04/27/1992


Related Activity
Type Activity Nr Safety Health
Accident 360300065
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 7 7
Current Violations 5 5
Initial Penalty $1,950 $0 $0 $0 $0 $1,950
Current Penalty $1,450 $0 $0 $0 $0 $1,450
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 510001 A 01/07/1992 01/16/1992 $300 $300 $0 01/17/1992 Y - State Decision  
2. 01001B Serious 19100303 B02 01/07/1992 01/16/1992 $0 $0 $0 01/17/1992 Y - State Decision  
3. 01002 Serious 19100025 D02 XII 01/07/1992 01/13/1992 $200 $200 $0 01/17/1992 Y - State Decision Citation has been deleted.
4. 01003 Serious 19100212 A05 01/07/1992 01/13/1992 $250 $250 $0 01/17/1992 Y - State Decision  
5. 01004 Serious 19100304 F04 01/07/1992 01/13/1992 $300 $300 $0 01/17/1992 Y - State Decision Citation has been deleted.
6. 01005 Serious 19100305 B01 01/07/1992 01/13/1992 $300 $300 $0 01/17/1992 Y - State Decision  
7. 01006 Serious 19100305 J04 IIA 01/07/1992 01/13/1992 $300 $300 $0 01/17/1992 Y - State Decision  
8. 01007 Serious 19100334 A02 II 01/07/1992 01/14/1992 $300 $300 $0 01/17/1992 Y - State Decision  

Investigation Summary

Investigation Nr: 894832
Event: 08/20/1991
ELECTRIC SHOCK - GROUND FAULT IN REFRIGERATOR

AN EMPLOYEE WAS APPARENTLY REMOVING REFRIGERANT FROM A COMPRESSOR ATOP A WALK-IN REFRIGERATOR. HE WAS ELECTROCUTED BY A GROUND FAULT IN THE REFRIGERATION EQUIPMENT. THE INVESTIGATION OF THIS ACCIDENT REVEALED THAT ONE OF THE THREE SOLID MOTOR CIRCUIT CONDUCTORS BETWEEN THE CONTACTOR BOX AND THE COMPRESSOR MOTOR HAD BURNED AS IT CONTACTED THE 0.375-INCH FLEXIBLE CONDUIT IN WHICH THE CONDUCTORS RAN. THE CONNECTOR FOR THE FLEXIBLE CONDUIT HAD NOT BEEN TIGHTENED, AND THE COMPRESSOR WAS PROTECTED BY A 20-AMPERE BREAKER INSTEAD OF THE REQUIRED 15-AMPERE FUSED DISCONNECT SWITCH. THE CONDUCTOR THAT WAS BURNED SHOWED SIGNS OF BEING DAMAGED WHEN IT WAS ORIGINALLY INSTALLED.

Keywords: OVERCURRENT PROTECT, ELECTRICAL, ELECTRIC CABLE, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 112397591 Fatality Electric Shock Heating, air conditioning, and refrig. mechanics
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close