Inspection Detail
Inspection: 112197520 - Owen'S Brockway
Inspection Information - Office: Monrovia District Office
Site Address:
Owen'S Brockway
1331 East Philadelphia Avenue
Pomona, CA 91766
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3221
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/30/1991
Emphasis:
Case Closed: 05/17/1995
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 361279227 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 2 | 3 | |||
Current Violations | 1 | 2 | 3 | |||
Initial Penalty | $1,000 | $0 | $0 | $0 | $0 | $1,000 |
Current Penalty | $1,000 | $0 | $0 | $0 | $0 | $1,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 23200002 A04 | 08/30/1991 | 09/30/1991 | $0 | $0 | $0 | - | ||
2. | 01002 | Other | 23400016 A | 08/30/1991 | 09/30/1991 | $0 | $0 | $0 | - | ||
3. | 02001 | Serious | 23200002 A03 | 08/30/1991 | 09/15/1991 | $1,000 | $1,000 | $0 | - |
Investigation Summary
TWO EMPLOYEES OF A GLASS CONTAINER MANUFACTURING COMPANY WERE REPAIRING A POWER DISCONNECT BOX LOCATED IN THE CEILING OF A PACKING ROOM IN THE PLANT. THE EMPLOYEES, WHO WERE NOT REGULARLY ASSIGNED THE TASK THEY WERE PERFORMING, WERE STANDING ON THE BED OF A MACHINE TO PERFORM THE JOB. ONE OF THEM WAS PERFORMING THE ELECTRICAL WORK, AND THE OTHER WAS HELPING HIM. THE 480-VOLT, THREE-PHASE SUPPLY FOR THE DISCONNECT WAS NOT DEENERGIZED BEFORE THE EMPLOYEES STARTED WORKING. ACCORDING TO THE EMPLOYER, THE EMPLOYEE PERFORMING THE ELECTRICAL WORK WAS USING A METER TO CHECK THE VOLTAGE, PLACING ONE PROBE ON THE PHASE CONDUCTOR AND ONE PROBE ON GROUND. AN ELECTRICAL FAULT OCCURRED, AND THE ENSUING ELECTRIC ARC BURNED THIS EMPLOYEE ON THE FACE. HE WAS HOSPITALIZED FOR 5 DAYS FOR HIS INJURY. HIS HELPER SUFFERED A CONTUSION TO HIS RIGHT SHOULDER WHEN HE FELL FROM THE MACHINE TO THE FLOOR. HE WAS TREATED AT A HOSPITAL AND RELEASED THE SAME DAY.
Keywords: BURN, ELECTRIC ARC, E GI III, ELECTRICAL, ELECTRICAL WORK, TEST EQUIPMENT, ELECTRICAL BOX, ELECTRICAL FAULT, UNTRAINED
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 112197520 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported | ||
2 | 112197520 | Hospitalized injury | Bruise/Contus/Abras | Occupation not reported |